57
11 Supplement
VEGAPULS 65 • Foundation Fieldbus
36518-EN-140209
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN
61298-1
Ʋ
Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ
Relative humidity
45 … 75 %
Ʋ
Air pressure
860 … 1060
mbar/86
… 106
kPa (12.5
… 15.4
psig)
Installation reference conditions
Ʋ
Min. distance to installations
>
200
mm (7.874
in)
Ʋ Reflector
Plane plate reflector
Ʋ False reflections
Biggest false signal, 20
dB smaller than the useful signal
Deviation with liquids
See following diagrams
1,0 m (3.28 ft)
20 mm (0.788 in)
8 mm (0.315 in)
- 8 mm (- 0.315 in)
- 20 mm (- 0.788 in)
0
1
2
3
Fig. 31: Deviation under reference conditions
1 Reference plane
2 Antenna edge
3 Recommended measuring range
Repeatability
≤ ±1 mm
Variables influencing measurement accuracy
Temperature drift - Digital output
±3
mm/10
K relating to the max. measuring range or
max.
10 mm
Additional deviation through electromag
-
netic interference acc. to EN
61326
<
±50
mm
Characteristics and performance data
Measuring frequency
C-band (6 GHz technology)
Measuring cycle time approx.
350 ms
Step response time
1)
≤ 3 s
Beam angle
2)
24°
Emitted HF power (depending on the parameter adjustment)
3)
Ʋ
Average spectral transmission power
density
-31 dBm/MHz EIRP
1)
Time span after a sudden measuring distance change by max. 0.5
m in liquid applications, max 2
m with bulk
solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).
2)
Outside the specified beam angle, the energy of the radar signal has a level which is reduced by 50 % (-3 dB)
3)
EIRP: Equivalent Isotropic Radiated Power