42
6 Set up with the display and adjustment module
VEGAPULS 65 • Foundation Fieldbus
36518-EN-140209
•
Peak values measured value:
Resetting of the measured min.
and max. distances to the actual measured value.
Select the requested reset function
[->]
and confirm with
[OK]
.
The following table shows the default values of VEGAPULS 65:
Menu section
Menu item
Default value
Setup
Measurement
loop name
Sensor
Medium
Liquid/Water
Bulk solids/Crushed stones, gravel
Application
Storage tank
Silo
Vessel form
Vessel bottom, dished boiler end
Vessel top, dished boiler end
Vesell height/
Measuring range
Recommended measuring range, see
"
Technical data
" in the supplement
Min. adjustment
Recommended measuring range, see
"
Technical data
" in the supplement
Damping
0.0 s
Display
Language
Like order
Displayed value
Distance
Display unit
m(d)
Scaling
0.00
%, 0
l
100.00
%, 100
l
Additional adjust
-
ments
Distance unit
m
Temperature unit
°C
Unit SV2
m
Probe length
Length of the standpipe Ex factory
Linearisation
curve
Linear
6.4 Saving the parameter adjustment data
We recommended noting the adjusted data, e.g. in this operating
instructions manual, and archiving them afterwards. They are thus
available for multiple use or service purposes.
If the instrument is equipped with a display and adjustment module,
the data in the sensor can be saved in the display and adjustment
module. The procedure is described in the operating instructions
manual "
Display and adjustment module
" in the menu item "
Copy
sensor data
". The data remain there permanently even if the sensor
power supply fails.
The following data or settings for adjustment of the display and ad
-
justment module are saved:
•
All data of the menu "
Setup
" and "
Display
"