4 Mounting
VEGAPULS 65 • Foundation Fieldbus
36518-EN-140209
Fig. 7: Recommended socket mounting
In case of very big socket diameters, the active antenna part can
be slightly recessed in the socket. The following rule applies to the
standard version of VEGAPULS 65: Socket diameter corresponds to
max. socket height.
In liquids, direct the sensor as perpendicular as possible to the prod
-
uct surface to achieve optimum measurement results.
Fig. 8: Alignment in liquids
The mounting location of the radar sensor should be a place where no
other equipment or fixtures cross the path of the microwave signals.
Vessel installations, such as e.g. ladders, limit switches, heating spi
-
rals, struts, etc., can cause false echoes and impair the useful echo.
Make sure when planning your measuring site that the radar sensor
has a "clear view" to the measured product.
In case of existing vessel installations, a false echo storage should be
carried out during setup.
If large vessel installations such as struts or supports cause false
echoes, these can be attenuated through supplementary measures.
Small, inclined sheet metal baffles above the installations scatter the
radar signals and prevent direct interfering reflections.
Sensor orientation
Vessel installations