6 Set up with the display and adjustment module
VEGAPULS 65 • Foundation Fieldbus
36518-EN-140209
The menu item "
Extend
" is used to extend an already created false
signal suppression. This is useful if a false signal suppression was
carried out with a too high level and not all false signals could be de
-
tected. When selecting "
Extend
", the distance to the product surface
of the created false signal suppression is displayed. This value can
now be changed and the false signal suppression can be extended to
this range.
A linearisation is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e.g. in a horizontal cylindri
-
cal or spherical tank - and the indication or output of the volume is
required. Corresponding linearisation curves are preprogrammed for
these vessels. They represent the correlation between the level per
-
centage and vessel volume. By activating the appropriate curve, the
volume percentage of the vessel is displayed correctly. If the volume
should not be displayed in percent but e.g. in l or kg, a scaling can be
also set in the menu item "
Display
".
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the
[ESC]
and
[->]
key.
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language, lighting, SIL and HART
mode.
The following reset functions are available:
•
Delivery status:
Restoring the parameter settings at the time
of shipment from the factory. A created false signal suppression,
user-programmable linearization curve, measured value memory
as well as event memory will be deleted.
•
Basic settings:
Resetting of the parameter settings incl. special
parameters to the default values of the respective instrument. Any
created false signal suppression, user programmable linearization
curve, measured value memory as well as event memory will be
deleted.
•
Setup:
Resetting of the parameter settings to the default values of
the respective instrument . Order-related settings remain but are
not taken over into the current parameters. User-generated false
signal suppression, user-programmed linearization curve, meas
-
ured value memory, echo curve memory as well as event memory
remain untouched. The linearization is set to linear.
•
False signal suppression:
Deleting a previously created false
signal suppression. The false signal suppression created in the
factory remains active.
Additional adjustments -
Linearization curve
Additional adjustments
- Reset