9 Diagnosis, asset management and service
VEGAPULS 67 • 4 … 20 mA/HART - four-wire
36532-EN-160224
Measurement error with constant level
Fault description
Error pattern
Cause
Rectification
1. Measured value
shows a too low or too
high level
Level
time
0
– Min./max. adjustment not
correct
– Adapt min./max. adjustment
–
Incorrect linearization curve
–
Adapt linearization curve
2. Measured value
jumps towards 100 %
Level
time
0
– Due to the process, the
amplitude of the product echo
decreases
– A false signal suppression was
not carried out
– Carry out a false signal sup-
pression
– Amplitude or position of a false
signal has changed (e.g. con-
densation, buildup); false signal
suppression no longer matches
actual conditions
– Determine the reason for the
changed false signals, carry out
false signal suppression, e.g.
with condensation
Measurement error during filling
Fault description
Error pattern
Cause
Rectification
3. Measured value
jumps towards 0 %
during filling
Level
time
0
– Amplitude of a multiple echo
(vessel top - product surface) is
larger than the level echo
– Check parameter "Application",
especially vessel top, type of
medium, dished bottom, high
dielectric constant, and adapt if
necessary
– The level echo cannot be distin-
guished from the false signal at
a false signal position (jumps to
multiple echo)
– Remove/reduce false signal:
minimize interfering installa
-
tions by changing the polariza
-
tion direction
– Chose a more suitable installa-
tion position
–
Transverse reflection from an
extraction funnel, amplitude of
the transverse reflection larger
than the level echo
– Direct sensor to the opposite
funnel wall, avoid crossing with
the filling stream
4. Measured val-
ue fluctuates around
10 … 20 %
Level
time
0
– Various echoes from an uneven
product surface, e.g. a material
cone
– Check parameter "Type of
medium" and adapt, if neces-
sary
–
Optimize installation position
and sensor orientation
–
Reflections from the product
surface via the vessel wall
(deflection)
– Select a more suitable installa-
tion position, optimize sensor
orientation, e.g. with a swivel-
ling holder
5. Measured value
jumps sporadically to
100 % during filling
Level
time
0
– Changing condensation or con-
tamination on the antenna
– Carry out a false signal sup-
pression or increase false
signal suppression with con-
densation/contamination in the
close range by editing
– With bulk solids use radar sen-
sor with purging air connection
or flexible antenna cover
Содержание VEGAPULS 63
Страница 24: ...24 4 Mounting VEGAPULS 67 4 20 mA HART four wire 36532 EN 160224 Fig 22 Purging air connection ...
Страница 81: ...81 Notes VEGAPULS 67 4 20 mA HART four wire 36532 EN 160224 ...
Страница 82: ...82 Notes VEGAPULS 67 4 20 mA HART four wire 36532 EN 160224 ...
Страница 83: ...83 Notes VEGAPULS 67 4 20 mA HART four wire 36532 EN 160224 ...