14
5 Set up with the display and adjustment module
VEGAPULS 62 • 4 … 20 mA/HART - four-wire
47121-EN-160215
3. Select in the menu item "
Application
" the vessel, the application
and the vessel form, for example, storage tank.
4. Carry out the adjustment in the menu items "
Min. adjustment
" and
"
Max. adjustment
".
The radar sensor measures the distance from the sensor to the
product surface. For indication of the real level, an allocation of the
measured distance to the percentage height must be carried out.
100%
0%
0,5 m (19.68
")
5 m
(196.9
")
2
1
3
Fig. 9: Parameter adjustment example min./max. adjustment
1 Min. level = max. measuring distance
2 Max. level = min. measuring distance
For this adjustment, the distance is entered when the vessel is full
and nearly empty. If these values are not known, an adjustment with
other distances, for example, 10 % and 90 % is also possible. Starting
point for these distance specifications is always the seal surface of
the thread or flange.
The function "
Echo curve memory
" makes it possible to save the echo
curve at the time of setup. This is generally recommended, and it is
Parameterization example
Diagnostics - Echo curve
memory