6 Set up with the indicating and adjustment module
VEGAFLEX 83 • 4 … 20 mA/HART - two-wire
41834-EN-120726
Note:
Check the distance to the product surface, because if an incorrect
(too large) value is entered, the existing level will be saved as false
signal. The filling level would then no longer be detectable in this area.
If a false signal suppression has already been created in the sensor,
the following menu window appears when selecting "
False signal
suppression
":
The instrument carries out an automatic false signal suppression as
soon as the probe is uncovered.
The menu item "
Delete
" is used to completely delete an already cre-
ated false signal suppression. This is useful if the saved false signal
suppression no longer matches the metrological conditions in the
vessel.
This menu item enables the setting of the requested national lan-
guage.
In the delivery status, the sensor is set to the ordered national lan-
guage.
In this menu item, you define the indication of the measured value
on the display. You can display two different measured values. In this
menu item, you define measured value 1.
The default setting for the displayed value 1 is "
Filling height Level
".
In this menu item, you define the indication of the measured value
on the display. You can display two different measured values. In this
menu item, you define measured value 2.
The default setting for the displayed value 2 is the electronics tem-
perature.
The optionally integrated background lighting can be adjusted via the
adjustment menu. The function depends on the height of the supply
voltage, see "
Technical data
".
Display/Menu language
Display/Displayed value 1
Display/Displayed value 2
Display/Backlight