4 Mounting
VEGAFLEX 83 • 4 … 20 mA/HART - two-wire
41834-EN-120726
Keep in mind that buildup can form on the spacers. Strong buildup
can influence the measurement.
1
2
3
Fig. 8: Position of the spacer or centering weight
1 Rod probe with spacer (PEEK)
2 Cable probe with centering weight
3 Spacer (PEEK) on the gravity weight of a cable probe
Note:
Measurement in a standpipe is not recommended for extremely
adhesive products.
Instructions for the measurement:
•
The 100 % point should not be above the upper tube connection
to the vessel
•
The 0 % point should not be below the lower tube connection to
the vessel
•
A false signal suppression with integrated sensor is generally
recommended to reach the maximum possible accuracy
To compensate the normal bias voltage loss due to the seal materials,
you have to use also disc springs in addition to the flange screws for
fastening PTFE plated flanges.
The flange screws of VEGAFLEX 83 must always be tightened with
a torque of approx. 60 Nm (44 lbf ft) so that the PTFE washer seals
reliably.
Torque with PTFE plated
flanges