5 Connecting to power supply
VEGAFLEX 83 • 4 … 20 mA/HART - two-wire
41834-EN-120726
Contact pin
Colour connection ca-
ble in the sensor
Terminal, electronics
module
Pin 4
Black
8
5.6 Wiring plan - version IP 66/IP 68, 1 bar
1
2
Fig. 17: Wire assignment fix-connected connection cable
1 brown (+) and blue (-) to power supply or to the processing system
2 Shielding
5.7 Switch-on phase
After connecting the instrument to power supply or after a voltage
recurrence, the instrument carries out a self-check for approx. 30 s:
•
Internal check of the electronics
•
Indication of the instrument type, hardware and software version,
measurement loop name on the display or PC
•
Indication of the status message "
F 105 Determine measured
value
" on the display or PC
•
The output signal jumps to the set error current
As soon as a plausible measured value is found, the corresponding
current is outputted to the signal cable. The value corresponds to the
actual level as well as the settings already carried out, e.g. factory
setting.
Wire assignment, con-
nection cable