6 Set up with the indicating and adjustment module
VEGAFLEX 83 • 4 … 20 mA/HART - two-wire
41834-EN-120726
This menu item is only available, if you have chosen interface meas-
urement under the menu item "
Application
". In this menu item you can
enter if there is a superimposed gas phase in your application.
Only set the function to "
Yes
", if the gas phase is permanently pre-
sent.
This menu item is only available if you have selected interface meas-
urement under the menu item "
Application
". In this menu item you can
choose the medium type of the upper medium.
You can directly enter the dielectric constant of the upper medium
or have it determined by the instrument. You have to enter the meas-
ured distance to the interface.
In this menu item you can enter the max. adjustment for the level. This
is the max. total level with interface measurement.
Adjust the requested percentage value with
[+]
and save with
[OK]
.
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. The distance refers to the sensor
reference plane (seal surface of the process fitting). Keep in mind that
the max. level must lie below the dead band.
Setup/Gas phase
Setup/Dielectric constant
Setup/Max. adjustment
- Level