6 Set up with the indicating and adjustment module
VEGAFLEX 83 • 4 … 20 mA/HART - two-wire
41834-EN-120726
Since the HART variables are very extensive, the indication was
divided into two menu items. In the menu item "
HART variables 1
"
you can have the first HART value PV (primary value) and the second
HART value SV (second value) of the sensor displayed.
A change of the values is not possible in the indicating and adjust-
ment module. To change these values, you have to use the adjust-
ment software PACTware.
Since the HART variables are very extensive, the indication was
divided into two menu items. In the menu item "
HART variables 2
" you
can have the third HART value TV (third value) and the fourth HART
value QV (quarter value) of the sensor displayed.
A change of the values is not possible in the indicating and adjust-
ment module. To change these values, you have to use the adjust-
ment software PACTware.
The following circumstances cause interfering reflections and can
influence the measurement:
•
High sockets
•
Vessel installations such as struts
Note:
A false signal suppression detects, marks and saves these false
signals so that they are no longer taken into account for the level and
interface measurement. We generally recommend carrying out a false
signal suppression to achieve the best possible accuracy. This should
be done with the lowest possible level so that all potential interfering
reflections can be detected.
Proceed as follows:
Enter the actual distance from the sensor to the product surface.
All interfering signals in this section are detected by the sensor and
stored.
Setup/HART variables 1
Setup/HART variables 2
Setup/False signal sup-
pression