6 Set up with the display and adjustment module
SOLITRAC 31 • Profibus PA
43834-EN-211203
You can have the value for "
Adjustment uncovered
" determined by
SOLITRAC 31.
This menu item appears only if you have selected "
Single point
adjustment
" as adjustment mode (Setup - Adjustment mode).
In this menu item you can adjust at which percentage value of the
max. pulse rate the sensor should switch over.
Since in most cases the radiation is almost completely absorbed
when the sensor is covered, the pulse rate when the sensor is cov-
ered is very low.
The change between the two statuses is sufficiently clear.
Hence a percentage value of 90 % for the Delta I value is recom-
mended.
You select lower values for sensitive detection of material cones or
buildup which cause only partial absorption of the radiation.
This menu item appears only if you have selected "
Two point ad-
justment
" as adjustment mode (Setup - Adjustment mode).
In this menu item you can set the min. pulse rate (ct/s) at which the
sensor should switch over.
Fill the vessel until the SOLITRAC 31 is covered.
You thus get the min. pulse rate (ct/s) for the "covered" adjustment.
Enter the requested pulse rate manually or let the rate be determined
by SOLITRAC 31. Automatic determination of the pulse rate should
be given preference.
You can enter the adjustment point (ct/s) manually.
You can let the adjustment point be determined by SOLITRAC 31.
Delta I (single point ad-
justment)
Adjustment "covered"
(two-point adjustment)