5 Connecting to power supply
SOLITRAC 31 • Profibus PA
43834-EN-211203
5.5 Set instrument address
An address must be assigned to each Profibus PA instrument. The
approved addresses are between 0 and 126. Each address must
only be assigned once in the Profibus PA network. The sensor is only
recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is set. This address can
be used to test the function of the instrument and to connect it to a
Profibus PA network. Then the address must be changed to integrate
additional instruments.
The address setting is carried out either via:
•
The address selection switch in the electronics compartment of
the instrument (address setting via hardware)
•
The display and adjustment module (address setting via software)
•
PACTware/DTM (address setting via software)
The hardware addressing is effective if an address <126 is set with
the address selection switches on the instrument. Software address-
ing is then no longer effective, the set hardware address applies.
2
1
3
1
1
2
4
5
6
22
11
12
21
22
19
20
18 17
14 13
16 15
12
9 10 11
Fig. 18: Address selection switch
1 Addresses <100 (selection 0), addresses >100 (selection 1)
2 Decade of the address (selection 0 to 9)
3 Unit position of the address (selection 0 to 9)
Software addressing is only effective if address 126 or higher is set
on the instrument with the address selection switches.
The addressing procedure is described in the operating instructions
manual "
Display and adjustment module
.
Instrument address
Hardware addressing
Software addressing