41
6 Set up with the display and adjustment module
SOLITRAC 31 • Profibus PA
43834-EN-211203
Default settings:
Resetting of the parameter adjustment like under
"
Basic settings
". In addition, special parameters are reset to default
values. Order-specific settings are deleted.
Peak values of measured value:
Resetting of the parameter adjust-
ments in the menu item "
Setup
" to the default values of the respec-
tive instrument. Order-specific settings remain but are not taken over
into the current parameters.
Peak values of temperature:
Resetting of the measured min. and
max. temperatures to the actual measured value.
The following table shows the default values of the instrument. The
values apply for the application "
Level
". First of all you have to select
the application.
Depending on the instrument version, not all menu items may be
available or they may be differently assigned:
Menu
Menu item
Default value
Setup
Sensor address
126
Measurement loop name
Sensor
Isotope
Cs-137
Application
Level
Background radiation
0 ct/s
Process value unit
%
Temperature unit
° C
Adjustment min.
Min. process value = 0 %
Adjustment max.
Max. process value = 100 %
Linearisation
0 ct/s = 100 %
90000 ct/s = 0 %
AI FB1 Channel
Process value
AI FB1 scaling unit
%
AI FB1 scaling
0 % = 0 %
100 % = 100 %
AI FB1 damping
0 s
Damping
60 s
Real value correction
0
Reference value - Relay
None
Lock adjustment
Released
Display
Language
Selected language
Displayed value
Pulse rate (ct/s)
With this function
•
Load parameter adjustment data from the sensor into the display
and adjustment module
Copy instrument settings