TLS-450 Setup and Operation Screens Manual
75
Leak Min. Annual (% full volume)
This value tells the system the minimum tank volume required to record a passed annual test. The value
reflects federal, state, and local requirements.
Allowable selections: 0 - 100%
Default: 0
Early Stop
When enabled this feature will prevent an In-Tank Leak Test from starting under the following conditions:
1. Fuel level is less than Leak Min. Periodic (0.2 gph test rate) or Leak Min. Annual (0.1 gph test
rate).
2. It is less than 8 hours from a delivery if Standard test or 5 hours from delivery for Quick test.
3. The product temperature is less than 0°F (-17.6°C) or more than +100°F (+37.4°C).
4. The fuel level is too low.
Allowable selections: Enabled, Disabled
Default: Disabled
Tank Test Notify
When "On" this feature triggers a warning allowing the operator to set a relay to shutdown the
submersible pump.
Allowable selections: On, Off
Default: Off
Tank Test Siphon Break
When "On" this feature allows the operator to perform in-tank leak tests on siphon manifolded tanks (a
siphon break valve must be installed for this selection).
Allowable selections: On, Off
Default:Off
Содержание TLS-450
Страница 1: ...Manual No 577013 940 Revision F Screens Manual TLS 450 Setup and Operation...
Страница 381: ...Web Access 6 Web Access Reports Inventory Page The TLS 450 Web Access Reports Inventory page example is shown below...
Страница 382: ...Appendix A 7 Web Access Reports Delivery Page The TLS 450 Web Access Reports Delivery page example is shown below...
Страница 384: ...Appendix A 9 Web Access Active Alarms Page The TLS 450 Web Access Active Alarms page is shown below...
Страница 385: ...Web Access 10 Web Access Priority Alarms Page The TLS 450 Web Access Priority Alarms page example is shown below...
Страница 386: ...Appendix A 11 Web Access Non Priority Alarms Page The TLS 450 Web Access Non Priority Alarms page example is shown below...
Страница 387: ...Web Access 12 Web Access Tanks Status Page The TLS 450 Web Access Tanks Status page example is shown below...
Страница 388: ...Appendix A 13 Web Access Tanks Alarm History Page The TLS 450 Web Access Tanks Alarm History page example is shown below...
Страница 391: ...Web Access 16 Web Access Lines Line Status The TLS 450 Web Access Lines Line Status page example is shown below...
Страница 392: ...Appendix A 17 Web Access Lines Alarm History Page The TLS 450 Web Access Lines Alarm History page example is shown below...
Страница 408: ...For technical support sales or other assistance please visit www veeder com...