TLS-450 Setup and Operation Screens Manual
238
Clear Table
You should manually clear the CSLD Rate Table if data, known to be inaccurate, had been stored in the
table and the source of the inaccurate data was subsequently removed (e.g., after making tank plumbing
repairs).
IMPORTANT! DO NOT CLEAR THE CSLD RATE TABLE UNLESS IT IS ABSOLUTELY
NECESSARY. DATA CLEARED FROM THIS TABLE CAN NOT BE RECOVERED!
Touch the Clear Table button to clear the 30 day CSLD rate table. You will be prompted to confirm this
action. The warning "Are you sure you want to clear the CSLD rate table?" is displayed, with OK and
Cancel buttons. If the OK button is selected, the dialog is closed, the CSLD rate table is cleared, and the
report is refreshed to reflect the change. If the Cancel button is selected, the dialog is closed and the
report view is unchanged. If the Clear Table button is selected when the current tank selection is "All
Tanks", the following error message is displayed: "This operation is valid for a single tank only".
Select Range
Touch this button to setup the report's contents:
•
Select Option List
- Select data for report: All Records, Day, Week, Month, Year, Date Range
•
Period Option List
- Select period: Previous, Previous n selections
•
Select Tank(s)
- Select tank(s) to report: "All Tanks" or "Current Tank"
Regulatory Compliance
Note: In-tank leak tests will not be declared a PASS unless the product level in the tank satisfies the
minimum product level defined in our Third Party certification for the leak test being performed. In-tank
leak tests performed with the product level below these minimum levels will be declared Invalid. Because
the minimum product level requirements vary with local, state, and federal regulations, you need to
ensure that the product level complies with the applicable regulations in your location.
Содержание TLS-450
Страница 1: ...Manual No 577013 940 Revision F Screens Manual TLS 450 Setup and Operation...
Страница 381: ...Web Access 6 Web Access Reports Inventory Page The TLS 450 Web Access Reports Inventory page example is shown below...
Страница 382: ...Appendix A 7 Web Access Reports Delivery Page The TLS 450 Web Access Reports Delivery page example is shown below...
Страница 384: ...Appendix A 9 Web Access Active Alarms Page The TLS 450 Web Access Active Alarms page is shown below...
Страница 385: ...Web Access 10 Web Access Priority Alarms Page The TLS 450 Web Access Priority Alarms page example is shown below...
Страница 386: ...Appendix A 11 Web Access Non Priority Alarms Page The TLS 450 Web Access Non Priority Alarms page example is shown below...
Страница 387: ...Web Access 12 Web Access Tanks Status Page The TLS 450 Web Access Tanks Status page example is shown below...
Страница 388: ...Appendix A 13 Web Access Tanks Alarm History Page The TLS 450 Web Access Tanks Alarm History page example is shown below...
Страница 391: ...Web Access 16 Web Access Lines Line Status The TLS 450 Web Access Lines Line Status page example is shown below...
Страница 392: ...Appendix A 17 Web Access Lines Alarm History Page The TLS 450 Web Access Lines Alarm History page example is shown below...
Страница 408: ...For technical support sales or other assistance please visit www veeder com...