TLS-450 Setup and Operation Screens Manual
46
•
MOMENTARY - The On/Off state is determined by assigned alarms/warnings. However, relay
returns to the inactive state after the Alarm button is touched to acknowledge the alarm.
•
PUMP COMM CONTROL - Select this relay type only when a set of line manifolded pumps are
using Red Jacket IQ Controllers, and you want to run PLLD precision line leak tests. After
selecting this relay type, when one IQ controlled pump of a manifolded set is turned On for line
leak testing, the relay will activate, blocking communication with the second IQ controlled pump
(giving the console total control of the pumps) until the precision test is complete.
Allowable selections:
•
Standard
•
Pump Control Output
•
Momentary
•
Pump Comm Control
Default: Standard
Orientation
You must identify the input switch orientation as either normally open or normally closed so the console
properly recognizes an ON or OFF condition.
Allowable selections: Normally Open, Normally Closed
Default: Normally Closed
Содержание TLS-450
Страница 1: ...Manual No 577013 940 Revision F Screens Manual TLS 450 Setup and Operation...
Страница 381: ...Web Access 6 Web Access Reports Inventory Page The TLS 450 Web Access Reports Inventory page example is shown below...
Страница 382: ...Appendix A 7 Web Access Reports Delivery Page The TLS 450 Web Access Reports Delivery page example is shown below...
Страница 384: ...Appendix A 9 Web Access Active Alarms Page The TLS 450 Web Access Active Alarms page is shown below...
Страница 385: ...Web Access 10 Web Access Priority Alarms Page The TLS 450 Web Access Priority Alarms page example is shown below...
Страница 386: ...Appendix A 11 Web Access Non Priority Alarms Page The TLS 450 Web Access Non Priority Alarms page example is shown below...
Страница 387: ...Web Access 12 Web Access Tanks Status Page The TLS 450 Web Access Tanks Status page example is shown below...
Страница 388: ...Appendix A 13 Web Access Tanks Alarm History Page The TLS 450 Web Access Tanks Alarm History page example is shown below...
Страница 391: ...Web Access 16 Web Access Lines Line Status The TLS 450 Web Access Lines Line Status page example is shown below...
Страница 392: ...Appendix A 17 Web Access Lines Alarm History Page The TLS 450 Web Access Lines Alarm History page example is shown below...
Страница 408: ...For technical support sales or other assistance please visit www veeder com...