TLS-450 Setup and Operation Screens Manual
353
Maintenance Operation
When to Perform
What To Do
Dispenser Pan Sensor
(Solid-State)
Yearly
A. Owner or Station Attendant
1. Inspect sensor cable for any
cracking or damage.
2. Verify sensor is firmly secured in an
upright position on the bottom of the
pan.
B. Service Contractor
1. Verify epoxy kits have been installed
on field wiring.
2. Replace sensor cable if cracked or
damaged (ref. item A.1).
Containment Sump
Sensor (Solid-State)
Yearly
A. Owner or Station Attendant
1. Inspect sensor cable for any
cracking or damage.
2. Verify sensor is firmly secured in an
upright position on the bottom of the
containment sump.
B. Service Contractor
1. Verify epoxy kits have been installed
on field wiring.
2. Replace sensor cable if cracked or
damaged (ref. item A.1).
Vapor Sensor
Yearly
A. Owner or Station Attendant
1. Inspect sensor cable for any
cracking or damage.
B. Service Contractor
1. Verify epoxy kits have been installed
on field wiring.
2. Replace sensor cable if cracked or
damaged (ref. item A.1).
Groundwater Sensor
Yearly
A. Owner or Station Attendant
1. Inspect sensor cable for any
cracking or damage.
2. Lift sensor above water level in the
well and verify the system activates
a 'WATER OUT' alarm.
B. Service Contractor
1. Verify epoxy kits have been installed
on field wiring.
2. Replace sensor if cable is cracked
or damaged (ref. item A.1).
3. If the sensor does not alarm (ref.
item A.2), replace the sensor.
Hydrostatic Sensor
Yearly
A. Owner or Station Attendant
1. Inspect sensor cable for any
cracking or damage.
B. Service Contractor
1. Remove sensor from brine reservoir
and verify floats move freely. With
Содержание TLS-450
Страница 1: ...Manual No 577013 940 Revision F Screens Manual TLS 450 Setup and Operation...
Страница 381: ...Web Access 6 Web Access Reports Inventory Page The TLS 450 Web Access Reports Inventory page example is shown below...
Страница 382: ...Appendix A 7 Web Access Reports Delivery Page The TLS 450 Web Access Reports Delivery page example is shown below...
Страница 384: ...Appendix A 9 Web Access Active Alarms Page The TLS 450 Web Access Active Alarms page is shown below...
Страница 385: ...Web Access 10 Web Access Priority Alarms Page The TLS 450 Web Access Priority Alarms page example is shown below...
Страница 386: ...Appendix A 11 Web Access Non Priority Alarms Page The TLS 450 Web Access Non Priority Alarms page example is shown below...
Страница 387: ...Web Access 12 Web Access Tanks Status Page The TLS 450 Web Access Tanks Status page example is shown below...
Страница 388: ...Appendix A 13 Web Access Tanks Alarm History Page The TLS 450 Web Access Tanks Alarm History page example is shown below...
Страница 391: ...Web Access 16 Web Access Lines Line Status The TLS 450 Web Access Lines Line Status page example is shown below...
Страница 392: ...Appendix A 17 Web Access Lines Alarm History Page The TLS 450 Web Access Lines Alarm History page example is shown below...
Страница 408: ...For technical support sales or other assistance please visit www veeder com...