TLS-450 Setup and Operation Screens Manual
106
Pumps and Lines Setup - All Lines
The line leak detection system cannot test a line when AC power to the submersible pump is shut off.
Since the line leak system automatically attempts to conduct a test whenever it receives a signal that the
dispenser is off, it is necessary to lock out line tests when the station or fueling site is shut down and
submersible pump power is off. In some areas, regulations prohibit leaving power to submersibles
switched on during hours when the site is unattended. The Line Lockout Schedule provides a flexible
means of locking out line leak tests in accordance with business hours.
The Lockout schedule identifies the hours not to run line leak tests for the station.
Allowable selections: Disabled, Daily, Individual (see explanations below). Default: Disabled
Line Lockout Schedule - Daily
Daily schedule allows you to enter a Lockout Start Time and Stop Time. The lockout period will begin and
end at the times you enter every day of the week. Note: By using a Daily schedule and entering the same
Start and Stop Times, you can lock out the line leak test function 24 hours per day.
Start Time
Allowable selections: HH:MM am/pm. Default: 12 pm
Содержание TLS-450
Страница 1: ...Manual No 577013 940 Revision F Screens Manual TLS 450 Setup and Operation...
Страница 381: ...Web Access 6 Web Access Reports Inventory Page The TLS 450 Web Access Reports Inventory page example is shown below...
Страница 382: ...Appendix A 7 Web Access Reports Delivery Page The TLS 450 Web Access Reports Delivery page example is shown below...
Страница 384: ...Appendix A 9 Web Access Active Alarms Page The TLS 450 Web Access Active Alarms page is shown below...
Страница 385: ...Web Access 10 Web Access Priority Alarms Page The TLS 450 Web Access Priority Alarms page example is shown below...
Страница 386: ...Appendix A 11 Web Access Non Priority Alarms Page The TLS 450 Web Access Non Priority Alarms page example is shown below...
Страница 387: ...Web Access 12 Web Access Tanks Status Page The TLS 450 Web Access Tanks Status page example is shown below...
Страница 388: ...Appendix A 13 Web Access Tanks Alarm History Page The TLS 450 Web Access Tanks Alarm History page example is shown below...
Страница 391: ...Web Access 16 Web Access Lines Line Status The TLS 450 Web Access Lines Line Status page example is shown below...
Страница 392: ...Appendix A 17 Web Access Lines Alarm History Page The TLS 450 Web Access Lines Alarm History page example is shown below...
Страница 408: ...For technical support sales or other assistance please visit www veeder com...