10-35
10
CSLD Troubleshooting
Actual CSLD Test Problems Analyzed
0005080126 0 0.020 66.4 -107.4 69.0 -0.13 699 7014 141.5 5.5 276 0.000
0005080427 1 0.129 66.0 -107.3 69.1 -0.11 670 7014 30.5 8.5 276 0.000
0005082328 3 0.097 64.5 -107.3 70.3 -0.16 2854 2747 129.5 27.3 467 0.000
0005090218 3 0.051 64.1 -107.3 70.3 -0.14 2518 2747 140.5 30.3 467 0.000
0005092322 3 0.003 64.6 -83.9 71.2 -0.07 1982 5745 129.5 9.1 334 0.000
0005100213 0 0.036 64.4 41.9 71.2 -0.06 1749 5744 139.5 12.1 334 0.000
0005102331 3 0.039 63.7 30.1 71.2 -0.13 2855 1559 129.5 33.3 531 0.000
0005110222 3 0.036 63.4 35.6 71.0 -0.10 2520 1559 139.0 36.3 531 0.000
0005112319 3 0.048 62.5 -107.1 70.7 -0.04 2878 4154 129.5 15.0 404 0.000
0005120210 3 0.009 62.3 -72.8 70.7 -0.04 2540 4154 139.0 18.0 404 0.000
0005130136 2 0.030 69.8 -107.2 71.1 -0.24 824 6333 138.5 0.2 307 0.000
0005130437 0 0.077 69.1 -107.3 71.3 -0.17 723 6333 114.5 3.2 307 0.000
0005132347 3 0.028 67.1 -107.0 71.6 -0.22 3350 1342 129.5 22.2 545 0.000
0005140237 3 0.008 66.5 -107.2 71.4 -0.17 2956 1342 140.5 25.2 545 0.000
0005140537 3 0.038 66.0 -106.0 71.2 -0.16 2720 1342 66.5 28.3 545 0.000
0005142248 3 -0.013 60.1 -79.5 70.7 0.00 3087 3396 129.5 14.9 438 0.000
0005150138 3 0.007 60.1 -72.9 70.6 -0.00 2724 3396 140.5 17.9 438 0.000
0005150438 3 -0.051 60.1 -72.7 70.4 -0.00 2507 3396 45.0 20.9 438 0.000
0005152328 0 0.054 64.5 -94.8 70.4 -0.07 1260 5499 129.5 5.7 345 0.000
0005160218 0 0.013 64.3 -107.2 70.3 -0.06 1112 5499 140.5 8.7 345 0.000
0005162319 3 0.052 64.1 -106.1 69.7 -0.14 2548 1734 129.5 29.5 521 0.000
0005170209 3 0.020 63.7 -98.6 69.6 -0.12 2444 1734 32.0 32.5 521 0.000
0005170352 2 0.007 60.2 60.5 69.1 0.08 615 9215 68.0 0.2 131 0.000
0005172312 3 0.034 61.5 35.6 68.9 -0.02 2757 5141 129.5 19.3 361 0.000
0005180202 3 -0.010 61.5 -91.1 68.8 -0.02 2433 5141 140.5 22.3 361 0.000
__
I_I_ 76687IA1000_
IA1000
MAY 18, 2000 8:27
TANK 1 UNLEADED MAG NUMBER OF SAMPLES = 9445
1334.000 15481.000 15480.000 15480.000 15480.000 15482.000 15483.000 15485.000
15489.000 15494.000 15497.000 45689.000 20931.000 23464.000 23409.000 23962.000
24250.000 24810.000 45691.000
TANK 2 PLUS MAG NUMBER OF SAMPLES = 523
1309.000 22143.000 22143.000 22143.000 22143.000 22143.000 22145.000 22144.000
22145.000 22145.000 22146.000 45504.000 21342.000 22545.000 23465.000 24019.000
24086.000 24730.000 45503.000
TANK 3 PREMIUM MAG NUMBER OF SAMPLES = 462
1312.000 21871.000 21871.000 21871.000 21871.000 21871.000 21871.000 21871.000
21872.000 21871.000 21871.000 44889.000 21445.000 22442.000 22975.000 23510.000
23695.000 24592.000 44892.000
Analysis
From the IA52 command compare LRATE (-0.282) with AVLRTE (0.017). This shows that there is excessive
compensation. The most likely cause for excessive compensation is a false probe temperature reading. Examining
the IA52 command did not show erroneous thermistor values. However, examining the IA51 command showed
that the board temperature value was intermittently bad.
Solution
Replace probe and delete rate table.
Intermittent bad values.
Yet probe’s temperature
readings look good at
this time!