10
CSLD Troubleshooting
Actual CSLD Test Problems Analyzed
10-28
980617081507 16 5349.11 48.821 63.89 67.15 72.67
980617081537 15 5348.68 48.818 63.88 67.14 72.67
980617081607 10 5347.10 48.806 63.88 67.13 72.67
980617081637 15 5347.82 48.811 63.88 67.12 72.67
980617081707 23 5345.59 48.795 63.87 67.13 72.67
980617081737 24 5340.45 48.757 63.86 67.14 72.67
980617081807 23 5332.53 48.699 63.85 67.14 72.67
980617081837 23 5327.48 48.662 63.85 67.13 72.67
980617081907 22 5323.96 48.636 63.85 67.13 72.67
980617081937 18 5321.93 48.621 63.85 67.13 72.67
980617082007 14 5323.43 48.632 63.85 67.12 72.67
980617082037 19 5325.39 48.647 63.86 67.13 72.66
980617082107 23 5326.68 48.656 63.86 67.14 72.66
980617082137 22 5327.94 48.666 63.87 67.14 72.67
980617082207 23 5329.04 48.674 63.87 67.14 72.67
980617082237 24 5330.24 48.682 63.86 67.14 72.68
980617082307 12 5331.09 48.688 63.86 67.13 72.68
980617082337 24 5332.11 48.696 63.86 67.12 72.68
980617082407 22 5332.77 48.701 63.86 67.12 72.68
980617082507 23 5329.52 48.677 63.85 67.15 72.68
980617082537 22 5324.32 48.639 63.85 67.16 72.68
980617082607 12 5321.19 48.616 63.86 67.16 72.68
980617082637 24 5319.28 48.602 63.87 67.16 72.68
980617082707 23 5315.00 48.571 63.86 67.16 72.68
980617082737 24 5309.65 48.531 63.86 67.15 72.68
980617082807 23 5309.97 48.534 63.87 67.15 72.68
980617082837 23 5311.16 48.543 63.87 67.14 72.69
980617082907 13 5311.96 48.549 63.87 67.14 72.69
980617082937 12 5313.25 48.558 63.87 67.14 72.68
980617083007 24 5314.42 48.567 63.87 67.13 72.68
980617083037 23 5315.37 48.574 63.87 67.14 72.68
980617083107 24 5316.16 48.579 63.87 67.14 72.69
980617083137 22 5316.99 48.585 63.86 67.14 72.69
980617083207 21 5317.58 48.590 63.86 67.14 72.69
980617083237 15 5316.19 48.580 63.87 67.14 72.69
980617083307 23 5312.81 48.555 63.86 67.13 72.69
980617083337 20 5311.06 48.542 63.86 67.13 72.69
MOVING AVERAGE: 5311.55
DISPENSE STATE: ACTIVE 957.217224
Analysis
Tanks 1 and 2 are siphon manifolded, but they are incorrectly programmed in the console as single tanks.
Solution
Reprogram tanks 1 and 2 as manifolded and delete the rate table.