10
CSLD Troubleshooting
Actual CSLD Test Problems Analyzed
10-40
981120075512 30 3433.34 36.397 61.85 60.89 57.38
981120075542 31 3433.35 36.397 61.85 60.88 57.39
981120075612 31 3433.38 36.397 61.85 60.88 57.39
981120075642 30 3433.31 36.397 61.85 60.88 57.39
981120075712 30 3433.31 36.397 61.85 60.88 57.40
981120075742 30 3433.29 36.397 61.85 60.88 57.40
981120075812 31 3433.29 36.397 61.85 60.88 57.40
981120075842 30 3433.30 36.397 61.85 60.88 57.41
981120075912 30 3433.27 36.397 61.85 60.88 57.41
981120075942 30 3433.28 36.397 61.85 60.88 57.41
981120080012 30 3433.30 36.397 61.85 60.88 57.41
981120080042 30 3433.26 36.397 61.85 60.88 57.42
981120080112 31 3433.23 36.397 61.85 60.88 57.42
981120080142 30 3433.13 36.396 61.85 60.89 57.42
981120080212 31 3433.14 36.396 61.85 60.89 57.42
981120080242 30 3433.12 36.396 61.85 60.89 57.42
981120080312 30 3433.05 36.396 61.85 60.89 57.42
981120080342 31 3433.04 36.396 61.85 60.89 57.42
981120080412 30 3433.10 36.396 61.85 60.89 57.41
981120080442 31 3433.07 36.396 61.85 60.89 57.41
981120080512 30 3433.08 36.396 61.85 60.90 57.40
981120080542 30 3433.08 36.396 61.85 60.90 57.40
981120080612 30 3433.06 36.396 61.85 60.90 57.40
981120080642 31 3433.04 36.396 61.85 60.90 57.39
981120080712 31 3433.06 36.396 61.85 60.90 57.39
981120080742 30 3432.99 36.395 61.85 60.90 57.39
981120080812 30 3432.99 36.395 61.85 60.90 57.39
981120080842 31 3433.00 36.395 61.85 60.90 57.40
981120080912 30 3433.03 36.396 61.85 60.90 57.40
981120080942 31 3433.02 36.396 61.85 60.89 57.40
981120081012 30 3433.04 36.396 61.85 60.89 57.40
MOVING AVERAGE: 3433.07
DISPENSE STATE: IDLE 0.097659
Analysis
Examining the IA54 table showed that following a dispense the level continued dropping for a long period of time.
Inspecting the probe revealed that the floats had been installed upside down.
Solution
Reinstall floats correctly and delete rate table.