CSLD Troubleshooting
Actual CSLD Test Problems Analyzed
ANALYSIS OF RATE TEST (IA52)
The average leak rate (AVLRTE) is -0.259. The average leak rate is uncompensated so excessive compensation is
not an issue. This leak rate is not excessively high so blender/pump sense issues are probably not involved.
The tank label is SUPER so most likely it is not manifolded.
The DATE is recent so results are up to date.
The maximum number of tests is 80 and because C1 = 79 there are more than enough tests.
SOLUTION
The float was stuck in the riser. A collar was installed on the probe to prevent recurrences of this problem.
CSLD PROBLEM 2 - MANIFOLDED TANKS 1 AND 2 ARE FAILING
Reports I201, I51, IA52, and I752 were collected for analysis.
DIAGNOSTICS
I20100
STATION HEADER INFO
MAY 21, 2000 10:29 AM
TANK
VOLUME
TLC VOLUME
ULLAGE
HEIGHT
WATER
TEMP
1
2311
2303
3705
39.21
0.0
65.2
2
3276
3266
4746
41.07
1.6
64.1
3
4378
4365
5774
42.81
0.0
64.4
4
PRODUCT
REGULAR
REGULAR
S
ECONDARY
MIDGRADE
PREMIUM
2547
2548
7605
28.68
1.3
59.7
IA5200
JUN 11, 2000 12:00 PM
CSLD DIAGNOSTICS: RATE TEST
TK
DATE
LRATE
INTVL
ST
AVLRTE
VOL
C1
C3
FDBK
ACPT
THPUT
EVAP
RJT
1
9608220320
-0.834
28.4
2
-0.809
7909
58
30
20.3
21.7
32.37
0.000
0
2
9608220320
-0.834
28.4
2
-0.809
7909
58
30
20.3
21.7
29.56
0.000
0
3
9608220445
-0.008
25.8
1
0.005
4400
67
18
30.
21.7
21.23
0.000
0
4
9608220402
0.005
22.3
1
0.005
1893
80
13
45.0
44.8
24.45
0.000
0
I75200
JUN 11, 2000 10:30 AM
LINE LEAK TANK ASSIGNMENT
LINE
LABEL
TAN
1
PREMIUM
4
Line 1 should be labelled Regular and assigned to tank 1
2
MIDGRADE
3
Correct as is
3
REGULAR
1
Line 3 should be labelled Premium and assigned to tank 4