Displayed Alarm Messages
6
Printer Error
(TLS4/TLS-450PLUS only)
P
Printer feed roller release is open..
Push the release lever to the up position.
Printer Error
(TLS-3XX only)
System
Probe Out
T
Hardware failure - probe or interconnecting wiring
to console.
Call for service following the procedures
established for your site.
Pump Out Alarm
Pm
A relay or external input has a Device Out alarm
active and the pump(s) that use that device will
not pump gas. Note that if a pump goes into
Device out, the Line it is on will go into ‘Device
Out’ as well.
Call for service following the procedures
established for your site.
Sensor Open Alarm
Q
Pressure sensor reading is less than -8 psi
(-55.16 kPa). Only tested while the pump is run-
ning. Dispensing halts if programmed to do so.
3 gph (11.3 lph) test must pass to clear the
alarm. Call for service following the proce-
dures established for your site.
Sensor Out Alarm
L, G, C, H, V
The sensor setup was performed incorrectly or a
sensor is disconnected or is not functioning prop-
erly.
Call for service following the procedures
established for your site.
Setup Data Warning
All Devices
Device setup data problem.
Recheck device setup parameters.
Short Alarm
L, G, C, H, V
A short has occurred in the sensor wiring or in the
sensor.
Call for service following the procedures
established for your site.
Shutdown
Q
System shut down line because of failed line leak
test, or an alarm assigned to disable the line is
active.
Identify offending alarm, and refer to PLLD
alarms for corrective action.
Siphon Break Active Warn-
ing
T
Siphon break valve has shut down manifold for
tank test.
Clears when tank test completes.
Sudden Loss Alarm
T
System detects loss of fuel during an idle period.
Check for gross leak.
Water Out Alarm
G
Water level is below the float switch, making the
sensor ineffective.
Call for service following the procedures
established for your site.
Messa
g
e
Short
Device ID
Cause
Action