background image

Displayed Alarm Messages

6

Printer Error

(TLS4/TLS-450PLUS only)

Printer feed roller release is open..

Push the release lever to the up position.

Printer Error

(TLS-3XX only)

System

Probe Out

T

Hardware failure - probe or interconnecting wiring 
to console.

Call for service following the procedures 
established for your site.

Pump Out Alarm

Pm

A relay or external input has a Device Out alarm 
active and the pump(s) that use that device will 
not pump gas. Note that if a pump goes into 
Device out, the Line it is on will go into ‘Device 
Out’ as well.

Call for service following the procedures 
established for your site.

Sensor Open Alarm

Q

Pressure sensor reading is less than -8 psi 
(-55.16 kPa). Only tested while the pump is run-
ning. Dispensing halts if programmed to do so.

3 gph (11.3 lph) test must pass to clear the 
alarm. Call for service following the proce-
dures established for your site.

Sensor Out Alarm

L, G, C, H, V

The sensor setup was performed incorrectly or a 
sensor is disconnected or is not functioning prop-
erly.

Call for service following the procedures 
established for your site.

Setup Data Warning

All Devices

Device setup data problem.

Recheck device setup parameters.

Short Alarm

L, G, C, H, V

A short has occurred in the sensor wiring or in the 
sensor.

Call for service following the procedures 
established for your site.

Shutdown

Q

System shut down line because of failed line leak 
test, or an alarm assigned to disable the line is 
active.

Identify offending alarm, and refer to PLLD 
alarms for corrective action.

Siphon Break Active Warn-
ing

T

Siphon break valve has shut down manifold for 
tank test.

Clears when tank test completes.

Sudden Loss Alarm

T

System detects loss of fuel during an idle period.

Check for gross leak.

Water Out Alarm

G

Water level is below the float switch, making the 
sensor ineffective.

Call for service following the procedures 
established for your site.

Messa

g

e

Short 

Device ID

Cause

Action

Содержание TLS-3 Series

Страница 1: ...TLS System Warnings Alarms Manual No 577014 243 Revision A Troubleshooting Guide...

Страница 2: ...l or consequential damages in connection with the furnishing performance or use of this publication The information contained in this publication may be subject to change without notice This publicati...

Страница 3: ...the front panel red ALARM TEST key to silence the alarm The front panel warning and alarm lights cannot be turned off until the cause of the condition is cor rected The warning and alarm message s wi...

Страница 4: ...n tries Verify the address book settings for the con tact are correct i e modem device number phone number to dial verify the receiving device fax or modem is operational Con tact technical support fo...

Страница 5: ...failed Rerun in tank leak test If second test fails call for service HRM Reconciliation Alarm HRM Hourly Reconcilia tion Mode T Activated for a tank 90 minutes after the 24 hour average variance has...

Страница 6: ...iately follow the alarm reporting pro cedures established for your site Line Equipment Alarm Q A problem with the pressure measurement equip ment has been detected Call for service following the proce...

Страница 7: ...Delivery Ticket Warning T Delivery Ticket information has not been entered at the console Enter Delivery Ticket information No Dial Tone Alarm TLS4 TLS 450PLUS only Co System failed to detect an oper...

Страница 8: ...tablished for your site Sensor Out Alarm L G C H V The sensor setup was performed incorrectly or a sensor is disconnected or is not functioning prop erly Call for service following the procedures esta...

Страница 9: ...For technical support sales or other assistance please visit www veeder com...

Отзывы: