Displayed Alarm Messages

3

Email Failed Alarm

(TLS4/TLS-450PLUS only)

Co

The console did not successfully send email when 
configured to email.

Verify the address book settings for the con-
tact are correct (email address of recipient), 
verify network connectivity is available 
(Ethernet card is installed). Contact techni-
cal support for assistance.

Fuel Alarm

L, G, C, H, V

Fuel is present in the area being monitored by the 
sensor.

Call for service following the procedures 
established for your site.

Fuel Out Alarm

Q

Tank product level below 10-inch (25.4 cm) level - 
cannot pump when active.

Schedule a delivery.

Fuel Quality Alarm

T

Water/phase separation may be present in tank.

Test fuel at bottom of tank to ensure water/
phase separation is not present. 

Generator Off

I

Backup generator shut down, in-tank leak testing 
resumed.

None

Generator On

I

Backup generator switched on, in-tank leak test-
ing halted.

None

Gross Test Fail Alarm

Q

3 gph (11.3 lph) line test failure. Dispensing halts, 
if programmed to do so, while the alarm is active.

Consult PLLD Alarm Quick Help Guide and 
PLLD diagnostic screens.

Gross Leak Test Fail Alarm

T

In-tank leak (3.0 gph [11.3 lph]) test failed.

Rerun in-tank leak test. If second test fails, 
call for service.

HRM Reconciliation Alarm

(HRM = Hourly Reconcilia-
tion Mode)

T

Activated for a tank 90 minutes after the 24-hour 
average variance has exceeded the preset HRM 
limits.

Review HRM hourly diagnostics. Contact VR 
Technical Support if variance cannot be 
resolved. 

High Liquid Alarm

L

Dispenser Pan/Containment Sump Sensors

Liquid reached 8" (203mm) on the dispenser pan 
sensor or 10" (254mm) on the containment sump 
sensor.

Immediately follow the alarm reporting pro-
cedures established for your site.

Dual-Float Differentiating Hydrostatic Sensor

A sensor in a brine-filled interstice detects an 
increase in the brine level increase. Liquid is 
entering the riser pipe, or in a high groundwater 
area, an outer wall rupture has occurred.

Call for service following the procedures 
established for your site.

H

The sensor detects a high liquid level.

Call for service following the procedures 
established for your site.

High Product Alarm

T

Product level in tank rose above programmed 
limit.

Do not allow additional delivery until product 
is dispensed below preset limit.

High Water Alarm

T

Water detected in tank exceeds programmed 
alarm limit.

Remove water from tank.

High Water Warning

T

Water detected in tank exceeds programmed 
warning limit.

Remove water from tank.

Messa

g

e

Short 

Device ID

Cause

Action

Содержание TLS-3 Series

Страница 1: ...TLS System Warnings Alarms Manual No 577014 243 Revision A Troubleshooting Guide...

Страница 2: ...l or consequential damages in connection with the furnishing performance or use of this publication The information contained in this publication may be subject to change without notice This publicati...

Страница 3: ...the front panel red ALARM TEST key to silence the alarm The front panel warning and alarm lights cannot be turned off until the cause of the condition is cor rected The warning and alarm message s wi...

Страница 4: ...n tries Verify the address book settings for the con tact are correct i e modem device number phone number to dial verify the receiving device fax or modem is operational Con tact technical support fo...

Страница 5: ...failed Rerun in tank leak test If second test fails call for service HRM Reconciliation Alarm HRM Hourly Reconcilia tion Mode T Activated for a tank 90 minutes after the 24 hour average variance has...

Страница 6: ...iately follow the alarm reporting pro cedures established for your site Line Equipment Alarm Q A problem with the pressure measurement equip ment has been detected Call for service following the proce...

Страница 7: ...Delivery Ticket Warning T Delivery Ticket information has not been entered at the console Enter Delivery Ticket information No Dial Tone Alarm TLS4 TLS 450PLUS only Co System failed to detect an oper...

Страница 8: ...tablished for your site Sensor Out Alarm L G C H V The sensor setup was performed incorrectly or a sensor is disconnected or is not functioning prop erly Call for service following the procedures esta...

Страница 9: ...For technical support sales or other assistance please visit www veeder com...

Отзывы: