Displayed Alarm Messages
3
Email Failed Alarm
(TLS4/TLS-450PLUS only)
Co
The console did not successfully send email when
configured to email.
Verify the address book settings for the con-
tact are correct (email address of recipient),
verify network connectivity is available
(Ethernet card is installed). Contact techni-
cal support for assistance.
Fuel Alarm
L, G, C, H, V
Fuel is present in the area being monitored by the
sensor.
Call for service following the procedures
established for your site.
Fuel Out Alarm
Q
Tank product level below 10-inch (25.4 cm) level -
cannot pump when active.
Schedule a delivery.
Fuel Quality Alarm
T
Water/phase separation may be present in tank.
Test fuel at bottom of tank to ensure water/
phase separation is not present.
Generator Off
I
Backup generator shut down, in-tank leak testing
resumed.
None
Generator On
I
Backup generator switched on, in-tank leak test-
ing halted.
None
Gross Test Fail Alarm
Q
3 gph (11.3 lph) line test failure. Dispensing halts,
if programmed to do so, while the alarm is active.
Consult PLLD Alarm Quick Help Guide and
PLLD diagnostic screens.
Gross Leak Test Fail Alarm
T
In-tank leak (3.0 gph [11.3 lph]) test failed.
Rerun in-tank leak test. If second test fails,
call for service.
HRM Reconciliation Alarm
(HRM = Hourly Reconcilia-
tion Mode)
T
Activated for a tank 90 minutes after the 24-hour
average variance has exceeded the preset HRM
limits.
Review HRM hourly diagnostics. Contact VR
Technical Support if variance cannot be
resolved.
High Liquid Alarm
L
Dispenser Pan/Containment Sump Sensors
Liquid reached 8" (203mm) on the dispenser pan
sensor or 10" (254mm) on the containment sump
sensor.
Immediately follow the alarm reporting pro-
cedures established for your site.
Dual-Float Differentiating Hydrostatic Sensor
A sensor in a brine-filled interstice detects an
increase in the brine level increase. Liquid is
entering the riser pipe, or in a high groundwater
area, an outer wall rupture has occurred.
Call for service following the procedures
established for your site.
H
The sensor detects a high liquid level.
Call for service following the procedures
established for your site.
High Product Alarm
T
Product level in tank rose above programmed
limit.
Do not allow additional delivery until product
is dispensed below preset limit.
High Water Alarm
T
Water detected in tank exceeds programmed
alarm limit.
Remove water from tank.
High Water Warning
T
Water detected in tank exceeds programmed
warning limit.
Remove water from tank.
Messa
g
e
Short
Device ID
Cause
Action