background image

Displayed Alarm Messages

4

iButton Fault Alarm

(TLS4/TLS-450PLUS only)

System

<No ID>

iButton failure.
System detected Damaged or Corrupted iButton. 
The warning has been active 20 days and has 
transitioned to an alarm. The alarm will be active 
a maximum of 10 days. After the duration of 30 
days, the user will be able to access only the fol-
lowing screens: About, Active Alarms, Alarm His-
tory, Priority Alarm, Maintenance Software and 
Ethernet Communication Setup.

Replace iButton with valid one.

iButton Fault Warning

(TLS4/TLS-450PLUS only)

System

<No ID>

iButton failure.
System detected Damaged or Corrupted iButton. 
Warning can be active a maximum of 20 days.

Replace iButton with valid one

Input Alarm

I

External device changed from programmed condi-
tion.

Check the operation of the external device.

Input Normal

I

(Not displayed, printed out only) External device 
returned to preset condition.

None

Invalid Fuel Level

T

Product level is too low, causing the fuel and 
water floats to be too close together.

Call for a delivery.

Leak Alarm

T

A static in-tank leak test failed.Rerun in-tank leak 
test.

Rerun in-tank leak test.

Leak Test Active

T

In-tank leak test is underway.

Do not dispense fuel from this tank until 
message disappears.

Liquid Warning

L, H

Liquid reached 1” (25.4 mm) on the dispenser 
pan or containment sump sensor.

Immediately follow the alarm reporting pro-
cedures established for your site.

Line Equipment Alarm

Q

A problem with the pressure measurement equip-
ment has been detected.

Call for service following the procedures 
established for your site.

Low Liquid Alarm

L

The sensor in a brine-filled interstice detects a 
decrease in the brine level. A hole is in the tank's 
inner wall, or in low groundwater areas, a hole is 
in the outer wall.

Call for service following the procedures 
established for your site.

Low Pressure Alarm

Q

Low pump dispense pressure is detected during a 
dispense. Dispensing halts if programmed to do 
so.

The next handle up will restart the pump.

Low Product Alarm

T

Tank level dropped below the programmed limit.

Call for a delivery.

Low Temperature Alarm

T

Probe temperature drops below -4°F (-20°C).

Probe returns to normal operation after 
probe temperature rises above 0°F
(- 17.8°C).

Mag Sensor Communica-
tion Alarm

MS, s

Hardware failure - sensor or interconnecting wir-
ing to console.

Call for service following the procedures 
established for your site.

Mag Sensor Fault Alarm

MS, s

Monitored parameter exceeded preset threshold.

Call for service following the procedures 
established for your site.

Mag Sensor Fuel Alarm

MS, s

Monitored parameter exceeded preset threshold.

Call for service following the procedures 
established for your site.

Mag Sensor Fuel Warning

MS, s

Monitored parameter exceeded preset threshold.

Call for service following the procedures 
established for your site.

Messa

g

e

Short 

Device ID

Cause

Action

Содержание TLS-3 Series

Страница 1: ...TLS System Warnings Alarms Manual No 577014 243 Revision A Troubleshooting Guide...

Страница 2: ...l or consequential damages in connection with the furnishing performance or use of this publication The information contained in this publication may be subject to change without notice This publicati...

Страница 3: ...the front panel red ALARM TEST key to silence the alarm The front panel warning and alarm lights cannot be turned off until the cause of the condition is cor rected The warning and alarm message s wi...

Страница 4: ...n tries Verify the address book settings for the con tact are correct i e modem device number phone number to dial verify the receiving device fax or modem is operational Con tact technical support fo...

Страница 5: ...failed Rerun in tank leak test If second test fails call for service HRM Reconciliation Alarm HRM Hourly Reconcilia tion Mode T Activated for a tank 90 minutes after the 24 hour average variance has...

Страница 6: ...iately follow the alarm reporting pro cedures established for your site Line Equipment Alarm Q A problem with the pressure measurement equip ment has been detected Call for service following the proce...

Страница 7: ...Delivery Ticket Warning T Delivery Ticket information has not been entered at the console Enter Delivery Ticket information No Dial Tone Alarm TLS4 TLS 450PLUS only Co System failed to detect an oper...

Страница 8: ...tablished for your site Sensor Out Alarm L G C H V The sensor setup was performed incorrectly or a sensor is disconnected or is not functioning prop erly Call for service following the procedures esta...

Страница 9: ...For technical support sales or other assistance please visit www veeder com...

Отзывы: