Displayed Alarm Messages
5
Mag Sensor High Liquid
Alarm
MS, s
Monitored parameter exceeded preset threshold.
Call for service following the procedures
established for your site.
Mag Sensor High Liquid
Warning
MS, s
Monitored parameter exceeded preset threshold.
Call for service following the procedures
established for your site.
Mag Sensor Install Alarm
MS, s
Sensor not installed in correct position.
Call for service following the procedures
established for your site.
Mag Sensor Low Liquid
Alarm
MS, s
Monitored parameter exceeded preset threshold.
Call for service following the procedures
established for your site.
Mag Sensor Low Liquid
Warning
MS, s
Monitored parameter exceeded preset threshold.
Call for service following the procedures
established for your site.
Mag Sensor Temperature
Warning
MS, s
Ambient temperature exceeded sensor’s operat-
ing range (-40 to +122°F [-40 to +50°C]).
Warning removed when temperature returns
to within sensor’s operating range.
Mag Sensor Water Alarm
MS, s
Monitored parameter exceeded preset threshold.
Call for service following the procedures
established for your site.
Mag Sensor Water Warn-
ing
MS, s
Monitored parameter exceeded preset threshold.
Call for service following the procedures
established for your site.
Maximum Product Alarm
T
Product level rose above the programmed limit.
Stop delivery. Do not allow additional deliv-
ery until product drops below preset limit.
Missing Delivery Ticket
Warning
T
Delivery Ticket information has not been entered
at the console.
Enter Delivery Ticket information.
No Dial Tone Alarm
(TLS4/TLS-450PLUS only)
Co
System failed to detect an operational line after 3
tries.
This alarm must stay active until it is con-
firmed that the alarm has been reported.
No CSLD Idle Time Warn-
ing
T
System has not had enough idle time over previ-
ous 24 hours to run a statistical leak detection
test.
Stop dispensing fuel from this tank until
CSLD test is complete.
Overfill Alarm
T
Fuel level has exceeded a programmed limit.
Potential overflow of tank may occur.
Stop delivery. Check for spillage.
Printer Out Of Paper
(TLS4/TLS-450PLUS only)
P
Paper roll is empty.
Replace the paper roll only with Veeder-Root
supplied paper rolls:
P/N 514100-456 - TLS-4/450PLUS
P/N 514100-210 - TLS-3XX
Printer Out Of Paper
(TLS-3XX only)
System
Periodic Test Fail Alarm
Q
0.2 gph (0.76 lph) test failure. Dispensing halts, if
programmed to do so.
Consult PLLD Alarm Quick Help Guide and
PLLD diagnostic screens.
Periodic Test Needed
Alarm
Q, T
A periodic in-tank leak (0.2 gph [0.76 lph]) test
has not been successfully completed within the
programmed number of days.
Schedule a 0.2 gph (0.76 lph) test.
Periodic Test Needed
Warning
Q, T
A periodic in-tank leak (0.2 gph [0.76 lph]) test
has not been successfully completed within the
programmed number of days.
Schedule a 0.2 gph (0.76 lph) test.
Periodic Leak Test Fail
Alarm
T
In-tank leak (0.2 gph [0.76 lph]) test failed. Dis-
pensing halts if programmed to do so.
Rerun in-tank leak test. If second test fails,
call for service.
Messa
g
e
Short
Device ID
Cause
Action