Mag-FLEX Installation And Handling Procedure
TLS Setup
24
TLS Setup
The TLS console Mag-FLEX setup is similar to that for a standard Mag Plus Probe setup. Listed below are the
setup exceptions.
•
Float Type
- For TLS2, TLS-3XX or TLS-450 consoles, the float type must be set as 3” FLOAT (76.2 mm).
Notes:
1. This is the default float type.
2. Water detection starts at 5” (127 mm) therefore water height warnings and alarms should be set above 5”.
3. See manual 577014-056 for setup instructions when installing a low level water float.
•
Tank Profile
- Select ‘Linear’ for TLS2, TLS-3XX or TLS-450 consoles, or ‘Multi-Point’ if an accurate tank
chart is available.
•
Tank Diameter
- For vertical cylindrical tanks, enter the full tank height here (NOT the diameter of the
cylinder). Full height is the distance from the bottom of the tank to the top of the cylinder excluding the domed
lid at the top of the tank. Set the height in mm.
Exit setup mode and check the inventory report, the water reading should now be “0”. Check all TLS setup
parameters are correct. If necessary, secure all console doors.