Mag-FLEX Installation And Handling Procedure
Mag-FLEX Probe-To-Surge Protector Wiring Connections
23
Figure 6. Removing Sealing Compound Clip
5. Thoroughly mix compound together. Invert bag several times while squeezing compound from one end to the
other for a minimum of one minute.
6. Once the mixture feels warm, immediately cut one corner and slowly fill the surge protector’s plastic sleeve.
Stop just short of filling the entire sleeve.
Do not overfill
. [Figure 7]
Figure 7. Pouring Sealing Compound Into Sleeve
7. With a twisting motion, rotate the outer clear plastic barrel to close the pouring slot.Wait at least five minutes,
then use the large cable tie to mount the surge protector to the riser pipe or probe canister as applicable.
8.
An earth cable must be connected between the surge protector and
a tank ground connection.
According to the provision of EN/IEC 60079-14, the minimum size of the earth cable shall be 4
mm².
Connect the green/yellow ground wire from the surge protector to an appropriate tank ground (see Figure 3 ).
13149-C