Mag-FLEX Installation And Handling Procedure
Mag-FLEX Probe Installation
18
9.
Fitting the process connection
10.
Securing the probe
Apply sealant to the thread of the process
connection. Carefully lower the process
connection into the tank entry fitting.
Screw in and tighten using a 55mm WAF
spanner..
Raise the probe canister until the exact
installation dimension that you measured &
recorded in step 8 is achieved.
Attention!
Do not raise the probe any higher as it will
become detached from the bottom of the
tank.
With the probe in this position tighten the
gland nut using a 30mm WAF spanner.
Secure the locking screw with the 5mm
Hexagon key.
Tighten process
connection
with 55mm
spanner
Then secure
socket cap
locking screw
with 5mm hex
key
Earth
connector
First tighten
gland with
30mm
spanner