background image

 

TCY-FT 

Configuration 

 

Doc: 70-00-0129B, V1.2, 2012-11-09 

© Vector Controls GmbH, Switzerland 

Page 8 

Subject to alteration 

www.vectorcontrols.com 

Input configuration 

Parameter  Description 

Range 

Default 

CP 18 

Configuration of remote input (X1) 

0 = Control Input  

1 = Comfort/Economy Mode switch 

2 = Comfort/OFF Mode switch  

3 = Keycard switch function   

4 = Output enable  

0…4 

CP 19 

Activation delay (minutes): 
The time the binary input needs to be open before Economy or 

OFF mode is activated. 

0…255 min 

CP 20 

Fixed setpoint for key card function in heating mode 

0–60°C (32..160°F) 

17°C (63°F) 

CP 21 

Fixed setpoint for key card function in cooling mode 

0–60°C (32..160°F) 

27°C (81°F) 

CP 22 

For TCY-FT2 only: Enable Auto changeover 

ON, OFF 

OFF 

CP 23 

For TCY-FT2 only: Auto changeover limit heating 

0–60°C (32..160°F) 

30°C (86°F) 

CP 24 

For TCY-FT2 only: Auto changeover limit cooling 

0–60°C (32..160°F) 

15°C (59°F) 

 

Configuring the function of the external input X1 

The external input X1 may be configured for several functions: 

 

CP18 = 0 

External control input 

The control input is provided by the external input. The internal input 

will not be used.  

CP18 = 1 

Switching Economy and 

Comfort modes 

Economy (unoccupied) and Comfort (occupied) modes are controlled 

through an external contact by connecting X1 through a dry contact to 

signal common. This function may be used together with key card 

switches for hotels or motion detectors for offices.

 

CP18 = 2 

Switching Energy Hold 

OFF and Comfort 

modes 

Opening the external temperature input will force the unit into the OFF 

operation mode. The operation mode cannot be overridden by using the 

terminal. Connecting the binary input to GND returns control of the 

operation mode to the terminal. This function may be used as window 

contact to prevent loss of energy.  

CP18 = 3 

Key card function 

As with CP18 = 1, the key card function switches economy 

(unoccupied) and comfort (occupied) modes. Instead of using the 

setpoint shift, the setpoints in unoccupied mode are defined by 

parameter CP20 and CP21.  

CP18 = 4 

Output enable 

This may be used for a dew point sensor input. Output will switch off if 

contact opens. 

 

Configuring auto changeover input X2 (TCY-FT2 only):  

The auto changeover function automatically changes heating and cooling mode based on supply media 

temperature or outdoor temperature. The difference between the two is in the values of the changeover limits 

CP23 and CP24. See table below for recommended settings. 

Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all signal 

ground levels of involved controllers must be the same in case more than one controller is switched.  

 

Recommended settings for CP23 and CP24: 

Change over mode 

Relation CP23 to CP24 

Example CP23 

Example: CP24 

Supply media 

CP23 > CP24 

25°C (77F) 

18°C (64F) 

Outside temperature 

CP23 < CP24 

15°C (59F) 

25°C (77F) 

Dry contact: Heating if contact closed 

CP23 > CP24 

25°C (77F) 

15°C (59F) 

Dry contact: Cooling if contact closed 

CP23 < CP24 

15°C (59F) 

25°C (77F) 

 

Содержание TCY-FT Series

Страница 1: ...l tool or software is required Name Ordering Item Name Item code Control Type Key data TCY FT2 W01 40 10 0067 1 Cooling only Compact PI controller with 2 TI 1 3 point output TCY FT2 W02 40 10 0067 2 H...

Страница 2: ...F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing...

Страница 3: ...4 5 above the floor in an area of average temperature Avoid exposure to direct sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind...

Страница 4: ...e connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY FT may display the following error condition Err1 The connection to the temper...

Страница 5: ...t a password using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parame...

Страница 6: ...FT2 W1 Cooling mode YC1 1 TCY FT2 W2 Heating mode YH1 2 TCY FT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY FT4 Heating and Cooling 4 pipe system YH1 YC1 TCY FT2 0 2 TCY FT4 0 3 TCY FT2 W1 0 TCY...

Страница 7: ...sed to fully open 0 255s 90s CP 14 Minimum running time FO1 TCY FT4 heating output The minimum time the output runs once it starts This setting prevents frequent switches with very short running times...

Страница 8: ...ion detectors for offices CP18 2 Switching Energy Hold OFF and Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overrid...

Отзывы: