Configuration 

 

Doc: 70-00-0129B, V1.2, 2012-11-09 

© Vector Controls GmbH, Switzerland 

Page 5 

Subject to alteration 

www.vectorcontrols.com 

Configuration parameters for firmware version 1.2 

The TCY-FT is preset to work for most applications. For special requirements it can be fine tuned to work ideally with a 

simple parameter setup routine. The parameters can be changed on the unit without the need of additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware version and revision. It is therefore important to use 

a matching product version and parameter set. The Firmware version and revision version can be found when pressing 

simultaneously the 

 and 

 keys during several seconds. On the upper 7 segment display, the firmware version can be 

found, on the lower 7 segment display the current revision index (or “sub-version”).  

Access to parameters 

The TCY-FT is an 

intelligent 

controller and can be adapted to fit perfectly into your application. The control operation is 

defined by parameters. The parameters are set during operation by using the standard operation terminal.  

The parameters are password protected. There are two levels of parameters: User operation parameters for access control 

settings and Expert parameters for control functions and unit setup. The passwords for user levels and expert levels are 

different. Only control experts should be given the control parameter password.  

The parameters can be changed as follows: 
 

1.

 

Press UP and DOWN button simultaneously for three seconds. The display will indicate the firmware version in the 

upper large digits and the revision in the lower small digits. Pressing any key will show: CODE. 

2.

 

Select a password using UP or DOWN buttons. Select 009 in order to get access to the user parameters, 241 for 

controls parameters.  

Press OPTION after selecting the correct password.  

3.

 

Once logged in, the parameter is displayed immediately 

4.

 

Select the parameters with the UP/DOWN keys. Change a parameter by pressing the OPTION key. The MIN and 

MAX symbols show up and indicate that the parameter may be modified now. Use UP and DOWN key to adjust 

the value. 

5.

 

After you are done, press OPTION or POWER in order to return to the parameter selection level.  

6.

 

Press the POWER key again so as to leave the menu. The unit will return to normal operation if no key is pressed 

for more than 5 minutes. 

User Parameters (Password 009) 

Parameter 

Description 

Range 

Default 

UP 00 

Enable access to operation modes 

ON, OFF 

ON 

UP 01 

Enable access to set points 

ON, OFF 

ON 

UP 02 

Not used 

ON, OFF 

OFF 

UP 03 

Enable manual change of Heating/Cooling Mode.  
No influence on TCY-FT2-W1 (cooling only) or TCY-FT2-W2 

(heating only) 

ON, OFF 

ON 

UP 04 

Not used 

ON, OFF 

OFF 

UP 05 

State after power failure:  

0 = off, 1 = on, 2 = state before power failure 

0, 1, 2 

UP 06 

Enable Economy (unoccupied) Mode.  

Shift the setpoint to a lower temperature in winter or higher 

temperature in summer in order to save energy. May be 

activated through the POWER button, or with the external 

input (typically for key card switches in hotel rooms or motion 

detectors for meeting rooms.)  

ON, OFF 

ON 

UP 07 

ON = Fahrenheit, OFF = Celsius 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibrate internal temperature sensor  
–10° to +10° in 0.1° steps. (Sensor is factory calibrated, use 

this feature for field adjustment only as required.)   

-10…10 

0.0 

UP 09 

Enable Frost Protection.  
Activates the output independent of operation mode when the 

control temperature drops below 5°C or 41°F. The controller 

returns to normal operation when the temperature increases 

above 10°C or 50°F. 

ON, OFF 

TCY-FT2-W1:   OFF 
TCY-FT2-W2:   ON 

TCY-FT2:  

ON 

TCY-FT4:  

ON 

 

 

Содержание TCY-FT Series

Страница 1: ...l tool or software is required Name Ordering Item Name Item code Control Type Key data TCY FT2 W01 40 10 0067 1 Cooling only Compact PI controller with 2 TI 1 3 point output TCY FT2 W02 40 10 0067 2 H...

Страница 2: ...F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing...

Страница 3: ...4 5 above the floor in an area of average temperature Avoid exposure to direct sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind...

Страница 4: ...e connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY FT may display the following error condition Err1 The connection to the temper...

Страница 5: ...t a password using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parame...

Страница 6: ...FT2 W1 Cooling mode YC1 1 TCY FT2 W2 Heating mode YH1 2 TCY FT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY FT4 Heating and Cooling 4 pipe system YH1 YC1 TCY FT2 0 2 TCY FT4 0 3 TCY FT2 W1 0 TCY...

Страница 7: ...sed to fully open 0 255s 90s CP 14 Minimum running time FO1 TCY FT4 heating output The minimum time the output runs once it starts This setting prevents frequent switches with very short running times...

Страница 8: ...ion detectors for offices CP18 2 Switching Energy Hold OFF and Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overrid...

Отзывы: