background image

 

TCY-FT 

Configuration 

 

Doc: 70-00-0129B, V1.2, 2012-11-09 

© Vector Controls GmbH, Switzerland 

Page 7 

Subject to alteration 

www.vectorcontrols.com 

Output configuration 

Parameter  Description 

Range 

Default 

CP 12 

Manual Override Mode:  

Allows manual control of the floating outputs for using the 

controller as positioner or during commissioning.  

ON, OFF 

OFF 

CP 13 

Running time FO1 (TCY-FT4 = heating output) 
The total time it takes for the actuator to run from fully open 

to fully closed or from fully closed to fully open 

0-255s 

90s 

CP 14 

Minimum running time FO1 (TCY-FT4 = heating output) 
The minimum time the output runs once it starts. This setting 

prevents frequent switches with very short running times.  

0-255s 

3s 

CP 15 

Running time FO2 (TCY-FT4 = cooling output) 
The total time it takes for the actuator to run from fully open 

to fully closed or from fully closed to fully open 

0-255s 

90s 

CP 16 

Minimum running time FO2 (TCY-FT4 = cooling output) 
The minimum time the output runs once it starts. This setting 

prevents frequent switches with very short running times. 

0-255s 

3s 

CP 17 

Maximum Output in Economy (unoccupied) Mode  

Reduces the load on the system when is the space is 

unoccupied.  

0 – 100 % 

50% 

 

 

Содержание TCY-FT Series

Страница 1: ...l tool or software is required Name Ordering Item Name Item code Control Type Key data TCY FT2 W01 40 10 0067 1 Cooling only Compact PI controller with 2 TI 1 3 point output TCY FT2 W02 40 10 0067 2 H...

Страница 2: ...F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing...

Страница 3: ...4 5 above the floor in an area of average temperature Avoid exposure to direct sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind...

Страница 4: ...e connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY FT may display the following error condition Err1 The connection to the temper...

Страница 5: ...t a password using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parame...

Страница 6: ...FT2 W1 Cooling mode YC1 1 TCY FT2 W2 Heating mode YH1 2 TCY FT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY FT4 Heating and Cooling 4 pipe system YH1 YC1 TCY FT2 0 2 TCY FT4 0 3 TCY FT2 W1 0 TCY...

Страница 7: ...sed to fully open 0 255s 90s CP 14 Minimum running time FO1 TCY FT4 heating output The minimum time the output runs once it starts This setting prevents frequent switches with very short running times...

Страница 8: ...ion detectors for offices CP18 2 Switching Energy Hold OFF and Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overrid...

Отзывы: