background image

 

TCY-FT 

Configuration 

 

Doc: 70-00-0129B, V1.2, 2012-11-09 

© Vector Controls GmbH, Switzerland 

Page 6 

Subject to alteration 

www.vectorcontrols.com 

Control Functions (Password 241) 

Warning! Only experts should change these settings! See user parameters for login procedure.  

Control configuration 

Parameter  Description 

Range 

Default 

CP 00 

Minimum setpoint limit in heating mode 

0-60°C (32-160°F) 

16°C (61°F) 

CP 01 

Maximum setpoint limit in heating mode 

0-60°C (32-160°F) 

30°C (86°F) 

CP 02 

Minimum setpoint limit in cooling mode 

0-60°C (32-160°F) 

18°C (65°F) 

CP 03 

Maximum setpoint limit in cooling mode 

0-60°C (32-160°F) 

30°C (86°F) 

CP 04 

Economy (unoccupied) Mode temperature shift: 
The comfort (occupied) setpoint is shifted by the value set 

with parameter. If heating is active the comfort setpoint will 

be decreased, if cooling is active, the setpoint will be 

increased. (Enable with UP06.)  

0-100°C (200°F) 

5.0°C (10°F) 

CP 05 

Dead Zone Span (TCY-FT4 only):  
The Dead Zone Span lies between the heating and the cooling 

setpoint. The output is off while the temperature is within the 

dead zone span. A negative dead zone is not possible. 

0-100°C (200°F) 

1.0°C (2°F) 

CP 06 

Heat/Cool Changeover Delay (TCY-FT4 only): 

A demand to switch between heating and cooling must persist 

for the length of time set with this parameter before the 

controller switches. Prevents activation of a sequence during a 

short-term change in temperature in order to protect 

equipment (with control overshoot for example)  

0-255 min 

5 min 

CP 07 

P-band heating X

PH

 

0-100°C (200°F) 

2.0°C (4.0°F) 

CP 08 

P-band cooling X

PC

 

0-100°C (200°F) 

2.0°C (4.0°F) 

CP 09 

K

IH

, Integral gain heating, in 0.1 steps, (TI is fixed to 4s) 

0 disables ID part 

low value = slow reaction 

high value = fast reaction 

0…25.5 

0.0 

CP 10 

K

IC

, Integral gain cooling, in 0.1 steps, 0 disables I part 

0…25.5 

0.0 

CP 11 

Configuration of operation mode 
0 = TCY-FT2-W1 = Cooling mode Y

C1 

1 = TCY-FT2-W2 = Heating mode: Y

H1 

2 = TCY-FT2 = Heating and Cooling (2 pipe system), Y

H1

 + Y

C1 

3 = TCY-FT4 = Heating and Cooling (4 pipe system), Y

H1

 + Y

C1 

TCY-FT2: 0 - 2 

TCY-FT4: 0 – 3 

TCY-FT2-W1: 0 

TCY-FT2-W2: 1 

TCY-FT2: 2 

TCY-FT4: 3 

 

Proportional control

 

(P-band)  

The proportional control function calculates the output based on the difference between setpoint and measured value. 

The proportional band (P-band) defines the difference between setpoint and measured value which will result in a 100% 

output. For example, with a heating or reverse 0-10v control sequence, and a 2.0°C (4.0°F) P-band value, at 10v the 

controller will be 2.0°C (4.0°F) below setpoint. This is the working range of the proportional control sequence. 

Setting the proportional band to 0 disables proportional control. 

 

 

Integral and Differential control

  

Proportional control is a very stable control mode. The flaw of proportional control alone, however, is that the setpoint 

is normally not reached. As the measured value gets closer to the setpoint, the output reduces until it reaches a point, 

a fraction above or below the setpoint, where the output equals the load. To reach the setpoint and achieve a higher 

level in comfort the Integral/Differential function should be activated.  

Integral Gain (KI) 

dynamically increases the output by the selected KI value until the setpoint is reached. The 

challenge, however, is to prevent hunting, where the output increases too fast, the temperature overshoots the 

setpoint, the output goes to 0, the temperature undershoots the setpoint, and the cycle repeats itself. Hunting may 
result if the integral gain

 

is too high. Each system is different. It is recommended to start with a KI value of 0.5 for 

water based systems and 1.0 for air based systems. Reduce this value if the measured value overshoots the setpoint 

by more than 1°C (2°F). Increase the value if the output takes too long to reach the setpoint. Air based systems 

react faster than water based systems.  

Setting the integral gain to 0 disables integral and differential control.  

 

Содержание TCY-FT Series

Страница 1: ...l tool or software is required Name Ordering Item Name Item code Control Type Key data TCY FT2 W01 40 10 0067 1 Cooling only Compact PI controller with 2 TI 1 3 point output TCY FT2 W02 40 10 0067 2 H...

Страница 2: ...F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing...

Страница 3: ...4 5 above the floor in an area of average temperature Avoid exposure to direct sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind...

Страница 4: ...e connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY FT may display the following error condition Err1 The connection to the temper...

Страница 5: ...t a password using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parame...

Страница 6: ...FT2 W1 Cooling mode YC1 1 TCY FT2 W2 Heating mode YH1 2 TCY FT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY FT4 Heating and Cooling 4 pipe system YH1 YC1 TCY FT2 0 2 TCY FT4 0 3 TCY FT2 W1 0 TCY...

Страница 7: ...sed to fully open 0 255s 90s CP 14 Minimum running time FO1 TCY FT4 heating output The minimum time the output runs once it starts This setting prevents frequent switches with very short running times...

Страница 8: ...ion detectors for offices CP18 2 Switching Energy Hold OFF and Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overrid...

Отзывы: