Installation, Operating & Maintenance Instructions
Series 651 DN 320-400 (I.D. 12“ - 16”), Logic
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 [email protected] www.vatvalve.com
267736ED
2008-02-26
19/53
Errors:
Description
Digit 1
Digit 2
Digit 3
Digit 4
Compressed air failure
(< 4 bar / 55 psi)
A I
R
f
Compressed air on exhaust
A I
R
x
Fatal error occurred
E
Error code. Refer to «Trouble shooting» for details
3.6 Setup
procedure
To enable this valve for pressure control setup steps 1 to 5 must be performed.
In case position control is required only it’s sufficient to perform steps 1 and 2.
Setup step
Description
1
POWER UP
Turn on ex 24VDC power supply (and external
±
15 VDC for sensor power
supply if required). Refer to chapter «Behavior during power up» for details.
2
INTERFACE
CONFIGURATION
Refer to chapter «Interface configuration» for details.
3
VALVE
CONFIGURATION
Basic configurations of the valve must be adapted according to application needs.
Refer to chapter «Valve configuration» for details.
4
ZERO
Compensation of the sensor offset voltage.
Refer to chapter «ZERO» for details.
5
LEARN
Determination of the vacuum system characteristic to accommodate the PID
controller. Refer to chapter «LEARN» for details.
Note: Without LEARN the valve is not able to run pressure control
3.6.1 Interface
configuration
Interface configuration must be adapted according to application needs.
•
Functionality of digital inputs CLOSE VALVE and OPEN VALVE must be selected.
These may be configured as ‘not inverted‘ or ‘inverted‘. Default is ‘not inverted‘.
•
LEARN range configuration for remote operation must be selected.
This may either be ‘full range’ or pressure limit according of analog SETPOINT input. Default is ‘full range‘.
Local operation
:
(‘Control View’, ‘Control Performance Analyzer’ or
‘Service Box 2‘)
Remote operation
:
Do configuration in menu ‘Setup / Interface’.
Note: It’s not possible to do ‘Interface configuration‘
via remote operation.