Installation, Operating & Maintenance Instructions
Series 612 DN 250 (I.D. 10”), EtherCAT
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 [email protected] www.vatvalve.com
282408EB
2012-04-23
26/81
3.4 Behavior in case of power failure
Valve position before
power failure:
Reaction of valve:
Without Power Failure Option (PFO)
612 . . - . .
G
. - . . . .
612 . . - . .
A
. - . . . .
Any
Valve remains at current position.
All parameters are stored in a power fail save memory.
For PFO retrofit and other options refer to chapter «Retrofit».
3.5 Display information
There is a 4 digit display located on the
panel. It displays configuration, status
and position information. For details
refer to following tables.
Power up:
Description
Digit 1
Digit 2
Digit 3
Digit 4
At first all dots are illuminated then
configuration is displayed:
Firmware version [e.g. 1E00]
(1
st
information for about 3s)
Controller configuration
(2
nd
information for about 3s)
In case
D999
is displayed, motor
interlock is active. Refer to
«Safety mode» for details.
1
E
0
0
J
= EtherCat
interface
0
= basic
1
= with SPS
1)
2
= with PFO
2)
3
= with SPS
1)
and PFO
2)
1
= 1 sensor version
2
= 2 sensor version
SYNC
indicates that powerup
synchronization is running.
S
Y
N
C
1) SPS = optional ±15 VDC Sensor Power Supply module
2) PFO = Power Failure Option
Display
1 2 3 4