Värmebaronen EP- 900, -1080, -1200, -1400
Technical data
Type
EP 900
EP 1080
EP 1200
EP 1400
Article number
4630
4632
4634
4636
RSK
Voltage,
power
control
400V3~
230V~
Voltage tolerance
≤ ±10
%
Frequency
50 / 60
Hz
Enclosure class
IP x1
Output
900
1080
1200
1400
kW
Current
1299
1559
1732
2021
A
Fuse
power,
≤
8 groups of 200
8 groups of 250
8 groups of 300
8 groups of 315
A
operation
6
A
Number of stages
30, can be limited down to 1 stage
Output/stage, stage size
30
36
40
46.6
kW
Current/stage
43.3
52
57.7
67.3
A
Cable flange
4 x FL 33, 2 x
∅
60 mm
Cable connection, area
8 x 95 - 240 Al/Cu
Up to 240 mm
2
round-pressed cable can be connected.
mm
2
Volume
610
litres
Calculation pressure
0.6
6
MPa
bar
Test pressure
0.86
8.6
MPa
bar
Calculation temperature
110
°C
Operating temperature
20 - 100
°C
Ambient temperature
≤
30
°C
Connection, flow/return
DN150 PN16
Safety pipe
2 x R50 utv
Flow requirements
recommended
∆
t=10°C
min/max
21.5
8.6/26.9
25.8
10.3/32.3
28.7
11.5/35.9
35.9
14.4/44.9
litres/
sec
litres/
sec
Weight empty
full of water
930
1540
kg
kg
Pressure drop
0
2
4
6
8
10
12
5
10
15
20
25
30
35
40
45
50
kPa
l/s
Ceiling height for immer-
sion heater replacement
>2500
mm
Manufactured to
PED 2014/68/EU article 4.3