24
Värmebaronen EP- 900, -1080, -1200, -1400
Electrical installation
Electrical installation must be carried out in accord-
ance with the applicable regulations, by an author-
ised electrical installer or by someone who is cov-
ered by the company's self-inspection programme!
Cables are dimensioned and installed according to current
electrical installation rules.
Cables must be laid so that it is possible to open the front
and remove the roof plate for service.
For minimum ceiling height, see Technical data.
Low-voltage cables may not be routed adjacent to power
lines as this may give rise to interference.
The boiler and heating system must be filled with water and
vented before the boiler is connected to the power supply.
Do not drill into the boiler's cover plates. Cuttings
can damage the boiler's electrical equipment!
M6 bolts are available for fastening cable trays.
Power supply
Removing the front roof plate facilitates the connection of the
power cables.
• Loosen the screws "a", as well as the square tube that holds
the doors.
• Remove the screws "b" and lift the front edge of the roof
plate so that it is straight up. Then lift the roof plate straight
up.
• Slide cable flanges and gaskets onto the power cables, tie
them up and connect the power cables.
• Screw the cable flanges in place with the gaskets.
• Reassemble.
a
b
b
Connect PE 4-conductor cables to switches and earth termi-
nals/clamps.
Tightening torque on switches is 31 Nm and 40 Nm on the
earth clamp.
Aluminium cable must be greased with neutral contact
grease.
Operating voltage
The control side of the boiler is supplied with 230V~, fused 6 A
The boiler must be preceded by an all-pole switch with at
least 3 mm breaking distance!
230V~
N
1 2 3 4 5 6 7 8 L 10
X01
N
N
N
N
1
3
Power supply to external unit
230V~, max load 2 A
1 2 3 4 5 6 7 8 L 10
X01
N
N
N
N
230V~
N
≤
2 A
1
External alarm indication
Buzzer alarm for external alarm indication of low water level,
overheating protection triggered, PEC or safety equipment
triggered.
Potential-free alternating contact, max. 230 V~, 2 A.
4
230V~
ALARM
N
1 2 3 4 5 6 7 8 L 10
X01
N
N
N
N
1
Circulation pump
See 'CP function' in the installation menu!
Potential-free closing contact for control to circulation pump,
max. load 230 V~, 2 A.
22
1
2
C
NO
≤
2 A
The circulation pump must be labelled to show that
it is controlled by the boiler if the function is used!