Värmebaronen EP- 900, -1080, -1200, -1400
Window one
ĮCURRENT LIMIT x.xxA
CURRENT MARGIN x.xxA
MAX PWR (30)xxxx.xkW
POWER SPEEDSTEP
EXT PWR LIMIT NO
EXT SET TEMP NO
CP FUNCTION NEVER
- - ï ï ï ï ï ï - -
ĮCURRENT LIMIT 1.00A
ĮCURRENT MARGIN 0.10A
No function!
MAX PWR (30)xxxx.xkW
Selection of the power with which the boiler is to operate.
The figures in brackets show the number of stages.
ĮPOWER SPEEDSTEP
Quick increase/reduction of power in connection with checks
and acceleration of the delay when it is active. If the delay is
active, the display shows
ĮSPEEDING TIME BLOCK
Release the button and press it again if you want quick
increase/decrease.
ĮEXT PWR LIMIT NO
Stage limit with external signal, 0-100% of selected power in,
MAX PWR (30)xxxx.xkW
.
NO
internal limit.
0-5V
limit with 0 - 5 V.
0-10V
limit with 0 - 10 V or potential-free blocking.
4-20mA limit with 4 - 20 mA.
ĮEXT SET TEMP NO
Temperature setpoint via external signal.
NO
internal setpoint.
0-5V
setpoint with 0-5 V (0 - 170°C).
0-10V
setpoint with 0-10 V (0 - 170°C).
4-20mA setpoint with 4-20 mA (0 - 170°C).
ĮCP FUNCTION NEVER
Operating method for circulation pump supplied with power
by the boiler:
NEVER no pump operation/pump switched off
AUTO
The pump starts before power is connected and
stops one minute after all power has stepped out. If
the pump is not in operation, it is run once daily. In
the event of over temperature, the pump starts and
is in operation until the over temperature situation
ends, even if all power is disconnected.
ALWAYS Pump always in operation.
ECO
Only with OTC, option.
Pump stop with maintenance operation, when the
outdoor temperature meets the set temperature
according to
ĮECO OUT TEMP +17°C
in
the Adjustment menu
Installation menu