Värmebaronen EP- 900, -1080, -1200, -1400
EP 1080 - Power Circuit
The control voltage is not broken by the load-break switches!
External voltage may occur.
To break the power supply to the boiler, the load-break switches must be placed
in 0 position.
Lock the switches!
See also "Technical data - component
placement"
U V W
PE
F5
K5
F6
K6
F7
K7
F8
K8
U V W
PE
F1
K1
F2
K2
F3
K3
F4
K4
B1
B2
B3
B4
PE
U W V
K13
F13
K14
F14
F15
K15
K16
F16
PE
U V W
K9
F9
K10
F10
K11
F11
K12
F12
Location on top of boiler vessel
Figures state location of immersion
heaters.
A. Temperature sensor
B. Temperature guard
C. Manometer connection
D. Level sensor
A
B
C
D
Power group
1 - 36 kW
Power group
2 - 72 kW
Power group
3 - 144 kW
Power group
4 - 288 kW
Power group
5 - 540 kW
Contactor
K1
K2
K3, K4
K5 - K8
K9 - K16
Immersion heater
18 kW
2, 4
7, 12, 15, 19 24, 34, 39, 40
25, 29, 30, 35
43, 46, 47, 51
8, 13, 20, 26
36, 41, 48, 52
54, 57, 59, 60
42, 45, 50, 53
5, 9, 16, 21
31, 37, 44, 49
55, 56, 58
6, 11, 14, 18
1, 3, 10, 17
23, 28, 33, 38
22, 27, 32
Fuse
3 x 80 A
3 x 125 A
3 x 160 A
F1
-
-
-
-
F2
-
-
F3, F4
-
-
F5-F8
-
F12, F16
F9 - F11, F13 - F15