14
VÄRMEBARONEN EP 31 300
Information on the menu
RUNTIME 0h
Peak BOILERTEMP XX°C
Peak PCB-TEMP XX°C
Actual PEC 000
Peak PEC 000
Actual CURRENT 0.00A
TOT LOW FLOW 0
Į - to MENU SELECTOR!
RUNTIME 0h
The time in hours for which the electronics were powered.
Peak BOILERTEMP XX°C
The highest boiler temperature since the electronics were
last switched on.
Peak PCB-TEMP XX°C
The highest temperature of the relay circuit board since the
electronics were last switched on.
Actual PEC 000
Peak PEC 000
Result of leakage current measurement The value, 1-500,
is a quality factor, i.e. the lower the value the better.
Actual CURRENT 0.00A
Requires that the load guard current transformer is installed.
During direct supply the current of the highest load phase is
shown.
During secondary measurement, the current measured by
the secondary current transformer, 1-5 A, is displayed.
The actual current value is obtained by multiplying the read
off value by the primary transformer’s conversion ratio.
TOT LOW FLOW 0
Number of low flow detections. If the boiler temperature
changes in an undesired way, the control detects this and
takes action to prevent unnecessary contactor operations
and to reduce the risk of the boiler’s temperature guard being
tripped. Check the flow through the boiler!