M
enu
s
11
VÄRMEBARONEN EP 31 300
Adjustment menu - with outdoor temperature compensation (UTK)
Adjustment menu - boiler with UTK -
Window one
ĮMAX TEMP SET 95°C
MIN TEMP SET 20°C
RESET PEAK VALUE(OK)
ECO TEMP, Tout 17°C
BOILER IN STANDBY? N
---- ïïïïïïïï ----
ĮMAX TEMP SET 95°C
ĮMIN TEMP SET 20°C
Setting range for temperature setpoint.
Max. limit: 50-105°C.
Min. limit: 20-45°C.
ĮRESET PEAK VALUE(OK)
Resetting the values in the information menu.
ĮECO TEMP(Tout) +17°C
Lowest temperature at which no heating is required. All boiler
power disconnected, the circulation pump is stopped.
Alternative
ĮCP function ECO
in the Instal-
lation menu muts be selected for the ECO-function top
be active and for temperature setting to be carried out
ĮBOILER IN STANDBY? N
Set boiler in standby position (switched off).
Window two
---- îîîîîîîî ----
Į P1, Tout= 20: 20°C
P2, Tout= 15: 27°C
P3, Tout= 10: 33°C
P4, Tout= 5: 40°C
P5, Tout= 0: 45°C
P6, Tout= -5: 49°C
---- ïïïïïïïï ----
Setpoint at outdoor
temperature:
20°C
→
15°C
→
10°C
→
5°C
→
0°C
→
-5°C
→
Window three
---- îîîîîîîî ----
Į P7, Tout=-10: 53°C
P8, Tout=-15: 57°C
P9, Tout=-20: 60°C
P10, Tout=-25: 62°C
P11, Tout=-30: 63°C
TEMP.ADJUST : 0°C
-to MENU SELECTOR!
Setpoint at outdoor
temperature:
-10°C
→
-15°C
→
-20°C
→
-25°C
→
-30°C
→
ĮTEMP.ADJUST : 0°C
Alternative temperature, against normal temperature,
+/- adjustment of setpoint, parallel displacement.
The change is affected by a contact function connected
to terminal block J2, see point 32 “Control circuit”
Heating curve
P1
P2
P3
P4
P5
P6
P7
P8
P9 P10 P11
+20 +15 +10 +5
0
-5 -10 -15 -20 -25 -30
70
60
50
40
30
20
80
Framledningstemperatur
Utomhustemperatur
Each setpoint, P1-P11, is adjustable over the range 20-80°C
Outdoor temperature
Fl
ow
te
m
pe
ra
tu
re