Config Params
Response Delay
The default for the L&J response delay is 2 mS.
2nd TX Address
Set this Address between 1 and 127 to have the
transmitter respond to a 2nd TankWay address. This
Address must be different than the Unit Addr (Basic
Setup) and the 3rd TX Address. Also, this address must
be different than all other transmitters on the same L&J
TankWay bus. The default value is 0 which means the
transmitter will not respond.
2nd Level Ref
This is set if the transmitter needs to respond to the a
second L&J TankWay address. This allows the
transmitter to send additional data items.
If the 2nd TX Address is set, this selects the data item in
the transmitter to be sent as the level portion of the L&J
TankWay message. The Encoder Type (Basic Setup)
determines the data range and resolution.
• 2000: 0 to 96 with a resolution of 0.01
• 1000/1500 Type 3: 0 to 255.9 with a resolution of
0.02
• 1000/1500 Type 4: 0 to 170.66 with a resolution of
0.003
2nd Temp Ref
This is set if the transmitter needs to respond to the a
second L&J TankWay address. This allows the
transmitter to send additional data items.
If the 2nd MS Address is set, this selects the data item in
the transmitter to be sent as the temperature portion of
the L&J TankWay message. This parameter is
transmitted in the range -819.0 to 819.0 with 0.1
resolution.
3rd TX Address
Set this Address between 1 and 127 to have the
transmitter respond to a 3rd L&J TankWay address. This
Address must be different than the Unit Addr (Basic
Setup) and the 2nd TX Address. Also, this address must
be different than all other transmitters on the same L&J
TankWay bus. The default value is 0 which means the
transmitter will not respond.
3rd Level Ref
If the 3rd TX Address is set, this selects the data item in
the transmitter to be sent as the level portion of the L&J
TankWay message.
The Encoder Type (Basic Setup)
determines the data range and resolution.
• 2000: 0 to 96 with a resolution of 0.01
• 1000/1500 Type 3: 0 to 255.9 with a resolution of
0.02
• 1000/1500 Type 4: 0 to 170.66 with a resolution
of 0.003
3rd Temp Ref
If the 3rd MS Address is set, this selects the data item in
the transmitter to be sent as the temperature portion of
the L&J TankWay message. This parameter is
transmitted in the range -819.0 to 819.0 with 0.1
resolution.
Содержание 2920
Страница 2: ......
Страница 16: ...2920 Float Tape Transmitter 1 Introduction 6 Installation and Operations Manual...
Страница 114: ...2920 Float Tape Transmitter 6 Bi Phase Mark 104 Installation and Operations Manual...
Страница 120: ...2920 Float Tape Transmitter 7 MODBUS 110 Installation and Operations Manual...
Страница 126: ...2920 Float Tape Transmitter 9 L J TankWay 116 Installation and Operations Manual...
Страница 138: ...2920 Float Tape Transmitter 11 Configuration Calibration Level Limits and Outputs 128 Installation and Operations Manual...
Страница 148: ...2920 Float Tape Transmitter 12 Maintenance and Troubleshooting 138 Installation and Operations Manual...
Страница 158: ...2920 Float Tape Transmitter 14 Ordering Information 148 Installation and Operations Manual...
Страница 178: ...2920 Float Tape Transmitter MODBUSAppendix A MODBUS Implementation 168 Installation and Operations Manual...
Страница 193: ......