11 Configuration & Calibration — Level, Limits, and Outputs
Varec, Inc.
127
5. Define the alarm conditions that can be used for outputs. At minimum, set values for the
following parameters:
CritLowLevel, AdvLowLevel, AdvHighLevel, CritHighLevel, LDeadband, CritLowTemp,
AdvLowTemp, AdvHighTemp, CritHighTemp, TDeadband, MinLevel, MaxLevel, MinTemp,
MaxTemp
Refer to “Tank Data” for information about the TANK point (parameter).
6. Set any other TANK parameters as appropriate.
7. Click the Exit button to return to the main screen.
8. Using the icons or the Point menu, select the DO point. The DO dialog box appears, show-
ing data items that can be modified in the following figure.
9. Assign a control & activation event to each direct output by defining parameters DO1As-
sign – D04Assign.
10. To make a relay active at system startup, set the appropriate register in the DOPwrUpState
parameter.
11. Click the Exit button.
12. Close ViewRTU.
13. Disconnect the laptop computer cable from the RS-232 connector.
14. Replace the 2920 FTT cover.
Содержание 2920
Страница 2: ......
Страница 16: ...2920 Float Tape Transmitter 1 Introduction 6 Installation and Operations Manual...
Страница 114: ...2920 Float Tape Transmitter 6 Bi Phase Mark 104 Installation and Operations Manual...
Страница 120: ...2920 Float Tape Transmitter 7 MODBUS 110 Installation and Operations Manual...
Страница 126: ...2920 Float Tape Transmitter 9 L J TankWay 116 Installation and Operations Manual...
Страница 138: ...2920 Float Tape Transmitter 11 Configuration Calibration Level Limits and Outputs 128 Installation and Operations Manual...
Страница 148: ...2920 Float Tape Transmitter 12 Maintenance and Troubleshooting 138 Installation and Operations Manual...
Страница 158: ...2920 Float Tape Transmitter 14 Ordering Information 148 Installation and Operations Manual...
Страница 178: ...2920 Float Tape Transmitter MODBUSAppendix A MODBUS Implementation 168 Installation and Operations Manual...
Страница 193: ......