Set the desired number of seconds before subsequent messages are displayed.
Figure 3-39
“UPS Configuration” dialog box
–
Click the “Minutes on battery before critical alarm” check box and set the amount of time
for the IPC to be on battery power once the UPS is in that mode (increased battery
power will allow longer time settings). When the time expires, the operating system
initiates a 30 second critical alarm timer and then begins the shutdown process.
9.
If desired, click the “When the alarm occurs, run this program” check box and enter the
program file in the field. When using this feature:
–
The command file must reside in
C:\Windows\system32
and have a file extension of
.exe, .com, .bat or .cmd.
–
Administrative privileges may be required.
–
Command files that initiate a dialog box and require user input cannot be used.
–
The command file must finish running within 30 seconds or it may impede the shutdown
process.
–
If desired, click the “Finally, turn off the UPS” check box to turn the uninterruptable
power supply off after a shutdown. This will prevent the battery from a complete
drawdown and result in longer battery life.
10. Click the “OK” button to return to the “Power Options Properties… UPS” dialog box.
11. Click the “Apply” button to save the configuration. When saved, click the “OK” button to
close the dialog box.
If pins 11 and 13 are connected through the DB-9 connector to monitor a low battery, the
low battery alarm may override the number of minutes the VL IPC will operate before
creating a critical alarm.
Содержание 2913181
Страница 12: ...Valueline IPC 1 6 PHOENIX CONTACT 2637_en_D...
Страница 24: ...Valueline IPC 2 12 PHOENIX CONTACT 2637_en_D...
Страница 74: ...Valueline IPC 4 10 PHOENIX CONTACT 2637_en_D...
Страница 82: ...Valueline IPC B 4 PHOENIX CONTACT 2637_en_D...
Страница 84: ...Valueline IPC B 6 PHOENIX CONTACT 2637_en_D...