Startup and Operation
2637_en_D
PHOENIX CONTACT
3-31
3.8.1
Power supply recommendations
The Valueline IPC requires a 24 V DC power source. This can be either a standard power
supply or a DC UPS. The following table provides expected amperage requirements for
different configurations.
3.8.2
QUINT-DC-UPS… installation
When using the QUINT-DC-UPS… uninterruptable power supply, there are two ways to
connect it to the Valueline IPC depending upon the level of monitoring/control desired.
–
Power connector: This connection method allows monitoring of the
Bat.-Mode
signal
via two terminals labeled
A
and
B
on the power connector. When the uninterruptable
power supply switches to battery power, it closes a contact to activate the Bat.-Mode
signal. The operating system starts the “Minutes on battery before critical alarm” timer,
if it is configured by the user (see Figure 3-39). If it is not configured, the operating
system starts the Critical Alarm timer which gives 30 seconds to launch and execute an
optional program before the VL IPC initiates the shutdown procedure.
–
Serial port (DB-9): This connection method provides additional communication
between the Valueline IPC and the uninterruptable power supply.
–
As in the power connection method, when the un interruptible power supply
switches to battery power, it closes a contact to activate the
Bat.-Mode
signal. The
operating system starts the “Minutes on battery before critical alarm” timer, if it is
configured by the user (see Figure 3-39). If it is not configured, the operating
system starts the Critical Alarm timer which gives 30 seconds to launch and
execute an optional program before the VL IPC initiates the shutdown procedure.
Table 3-2
Power requirements
Processor
Display
Power supply
output rating
Atom
No display
2.5 A
12- and 15-in. display
2.5 A
17- and 19-in. display
5 A
24-in. display
1
1
The 24-in. display requires an additional power connection
10 A
Celeron and Core2 Duo
No display
5 A
12-, 15-, 17- and 19-in.
display
5 A
10 A
Any configuration with PCI slots
No display
5 A
12-, 15-, 17- and 19-in.
display
5 A
10 A
Any program launched at this time is typically used to send an alert message to a system
administrator that the computer is shutting down. This program must reside in
C:\Windows\system32.
Содержание 2913181
Страница 12: ...Valueline IPC 1 6 PHOENIX CONTACT 2637_en_D...
Страница 24: ...Valueline IPC 2 12 PHOENIX CONTACT 2637_en_D...
Страница 74: ...Valueline IPC 4 10 PHOENIX CONTACT 2637_en_D...
Страница 82: ...Valueline IPC B 4 PHOENIX CONTACT 2637_en_D...
Страница 84: ...Valueline IPC B 6 PHOENIX CONTACT 2637_en_D...