Venting
Co-Linear Conversion
Note:
Co-linear
fl
exible aluminum venting should be
professionally inspected periodically for corrosion
and damage and replaced when necessary. If the
installation does not allow for future inspection or
replacement of the
fl
exible aluminum venting, then
stainless steel vent liners should be used.
Note:
Co-linear portion of vent system may only be
installed within a solid-fuel burning
fi
replace and
chimney.
Co-Linear Conversion Installations
The appliance can be adapted to co-linear applications
using an existing chimney. The appliance must not be
connected to a chimney
fl
ue serving a separate solid-
fuel burning appliance.
The appliance must be fully enclosed while maintaining
clearances to combustibles detailed elsewhere in this
manual.
Types of Installations
• Partial installation into an existing
fi
replace
• Installation into an adjacent chimney
See the following pages for each installation details.
Rules for Co-Linear Venting
• Maximum 40 feet vertical pipe
• Minimum 10 feet vertical
• Maximum o
ff
set 8 feet with liners at minimum
45 degrees from horizontal plane
• Restrictor: Set to Position 4 (see page 21).