44
X
8-5/8”
(219 mm)
2-13/16”
(71 mm)
7-3/8”
(188 mm)
8-3/8”
(213 mm)
Gas line stub
1/2” male npt
Electrical access/
Junction box
Rear of
appliance
Set-up Gas Supply
The gas supply inlet connec-
tion is a 1/2” NPT male line
stub located on the rear left
hand side of the appliance.
The unit is supplied with a stainless steel fl ex line to
allow the appliance to be disconnected for service. An
individual shut-off valve (supplied) is required on the
supply line ahead of the fl ex connector.
Use only new black iron or steel pipes or copper tubing
if acceptable—check local codes. Note that in USA,
copper tubing must be internally tinned for protection
against sulfur compounds.
Unions in gas lines should be of ground joint type.
The gas supply line must be sized and installed to
provide a supply of gas suffi cient to meet the maximum
demand of the appliance without undue loss of pressure.
Sealant used must be resistant to the action of all gas
constituents including LP gas. Sealant should be ap-
plied lightly to male threads to ensure excess sealant
does not enter gas lines.
Pressure test the supply line for leaks.
The appliance and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply pip-
ing system at test pressures equal to or less than 1/2
psig (3.5 kPa).
Failure to either disconnect or isolate the appliance
during pressure testing may result in regulator or valve
damages and void the warranty. Consult your dealer in
case of damages.
Pressure Test Points
The minimum supply pressure is given in the section
Speci
fi
cations
of this manual—page 23.
All piping and connections must be tested for leaks af-
ter installation or servicing. All leaks must be corrected
immediately.
When testing for leaks:
• Make sure that the appliance is turned off .
• Open the manual shut-off valve.
• Test for leaks by applying a liquid detergent or soap so-
lution to all joints. Bubbles forming indicate a gas leak.
Never use an open fl ame to check for leaks.
Correct any leak detected immediately.
The pressure test tapping locations are shown in the
fi gure below. An internal regulator within the valve con-
trols the burner manifold pressure. The correct pressure
range is shown in the table in section
Speci
fi
cations
of
this manual on page 23. The pressure check should be
made with the burner alight and at its highest setting.
See
Lighting Instructions
section for full operating details
on page 20.
Left side view
Installation
Manifold
Test
Pressure
Valve Inlet
Pressure
Manifold pressure
adjustment screw
located behind
plastic mushroom
cap.
Pressure Testing
QUALIFIED
INSTALLER