4.1 SENSOR/SWITCHING MODULES
4.1.2 SST N.C. SENSOR (34S)
Specifications
Configuration
(2) Universal voltage N.C. 2-wire solid state
sensors
(2) Wire terminations for one solenoid
Voltage range
20 - 250 VAC 50/60 Hz; 20 - 250 VDC
Minimum on current
2.0 mA
Maximum continuous current
0.1 amps
Maximum leakage current
<0.5 mA
Maximum voltage drop
6.7 volts @ 10 mA
7.5 volts @ 100 mA
Circuit protection
Protected against short circuits and direct
application of voltage with no load.
Solenoid pass-thru specifications
Solenoid voltage range
20 - 250 VAC 50/60 Hz; 20 - 250 VDC
Maximum solenoid current
0.75 amps
Wiring diagrams
1
NC
2
1
2
3
4
5
6
7
8
OPEN
SE
T C
LO
SE
D
SE
T
O
PE
N
Solenoid
Power
CLOSED
SOL
seconds
Push for 2
C
NC
C
SOL PWR
1
2
R
G
Red closed
1
NC
2
1
2
3
4
5
6
7
8
CLOSED
SE
T O
PE
N
SE
T
CL
O
SE
D
Solenoid
Power
OPEN
SOL
seconds
Push for 2
C
NC
C
SOL PWR
1
2
R
G
Green closed
Common receptacle options pin-out
MALE (PINS)
MALE (PINS)
1
1
2
2
5
5
4
4
3
3
5-PIN MICRO CONNECTOR (M12)
5-PIN MINI CONNECTOR
Signal
OPEN / CLOSED C
[Jumper installed]
CLOSED NC
OPEN NC
SOL PWR 1
SOL PWR 2
Pin
1
2
3
4
5
Signal
OPEN NC
CLOSED NC
SOL PWR 2
SOL PWR 1
OPEN / CLOSED C
[Jumper installed]
Pin
1
2
3
4
5
Signal
NOT USED
FEMALE (PINS)
FEMALE (PINS)
2
3
1
5
2
3
1
4
5-PIN MICRO CONNECTOR (M12)
3-PIN MINI CONNECTOR
NOT USED
SOL 2
SOL 1
NOT USED
Pin
1
2
3
4
5
Signal
NOT USED
SOL 2
SOL 1
Pin
1
2
3
Note
Consult factory for additional quick connector options.
Stonel product publication 105509revA | EC70EN- 6/2022
12