BCs160VA
Nov. 15, 1997
SMART-PULP
Smart Consistency Transmitter
22
Lower range-value in % Cs. Warning of going below the measurable lower
limit: refer to above text. Default: 2.0% Cs.
Upper range-value in % Cs. Warning of exceeding the recommended
upper limit: refer to above text. If span is too wide (> 30 N), SMART-PULP
will not accept the upper limit. In that case you have to lower the upper
limit and/or raise the lower limit. Span may also be too narrow (<0.8
%Cs), in which case you have to raise the upper limit and/or decrease the
lower limit. Default: 5% Cs.
Damping the fluctuation of the output signal, 1 to 60 seconds. Define at
least the minimum value required to damp harmful fluctuation. Only the
mechanical, approx. 2 s damping is provided if you define 1 s, in software.
The display’s language. The language of the country in question, or
English. Available options: Finnish, English, Swedish, French and
German.
Shear force unit: either G = gramme or N = Newton.
Temperature unit: either C = °C or F = °F. Default: C-G.
Mounting position. Options: HOR TOP = upper side of horizontal pipe,
HOR SIDE = side of horizontal pipe, VER UP = vertical pipe, upward flow.
Default: HOR TOP.
000...999. 000 defines no password protection. If you forget you password,
the protection can be canceled with a specific number combination. If the
password is other than 000, the prompt PASS = 0 will be displayed when
you change other parameters. To answer the prompt, give the correct
number combination with the arrow keys and then press ENTER. Default:
000.
HART® address: 0-15 or optionally the next item (MODB-ADD). Default:
0, i.e. normal installation with a single transmitter.
Sensor blade type: LL, JL, GL etc., and material: AISI, TITANium and
HASTElloy. Default: the supplied sensor. NOTE! Answering YES to SAVE
OK? question will restore the factory settings to the recipes (pulp type,
filler content and the P1 and P2 parameters. For this reason the blade
type parameter must always be changed first when sensor is replaced!
If the factory settings are not wanted and the blade type was not changed
use ESC button to escape the command.
Alarm. Either 3.7 mA or 22 mA output can be selected to indicate
transmitter failure. Default: 3.7 mA.
Measurement point’s tag code. Up to 8 characters, either letters or
numbers. (Currently selected character is indicated by an apostrophe at
the upper left corner.) Select a character with arrow keys. Accept the
selection with ENTER, then select the next character. You can move
forward from this parameter after handling all the required characters.
Transmitter’s type code. E.g. LL SS 2W ID, which can be changed in the
same way as TAG. Default: code of delivered transmitter.
Manufacturer’s version code, which you cannot change.
LOWER RA
UPPER RA
DAMPING
LANGUAGE
UNITS
MOUNTING
PASSWORD
HART-ADD
BLADE TY
ALRM TYP
TAG
TMTRTYPE
TMTRVERS